Plan Review Notes
Plan Review Notes For Permit 00031556
Permit Number 00031556
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-EGRESS WINDOW IN BEDROOM #2 DOESN'T
 COMPLY WITH SECTION 1005.4 SBC 1997.
 2-OPENINGS AT REAR ELEVATION EXCEED THE
 PERCENTAGE ALLOWED BY TABLE 600 SBC/97
 CALCULATIONS ON SHEET A-8 ARE MISSING
 THE SH H36 WINDOW BY BREAKFAST AREA.
 ALSO, SEE WINDOW AND DOOR PRODUCT
 APPROVAL FOR ACTUAL OPENING REQUIRED.
 THOSE ARE THE RIGHT NUMBERS TO USE FOR
 OPENING CALCULATIONS.
 3-UPDATE/REVISE ALL DRAWINGS AS REQUIRED
 SEE COMMENTS ON PLANS.USE SBC 97 NO 99
 4-ATTIC ACCESS TO BE 22"X36" MINIMUM.
 SECTION 2309.6 SBC 1997.
 5-PRODUCT APPROVALS:
 -PROVIDE COPIES OF TEST RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM E 330.
 SECTION 1706 SBC 1997.
 -DRAWINGS FOR OUTSWING ENTRY DOOR WITH
 LITES PRODUCT APPROVAL ARE NOT LEGIBLE
 6-STORM PANELS:
 -REVISE KEY PLAN AND INSTALLATION SCHED
 TO MATCH ARCHITECT'S PLAN ON SHEET A-8
 NOTE: WAIT TILL ARCHITECT REVISES PLAN
 TO MEET THE TABLE 600 REQUIREMENTS.
 -USE MASONRY ANCHOR SPACING WHEN PANELS
 ARE TO BE ATTACHED TO MASONRY COLUMNS
 WITH FILLED CELLS.
 7-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 8-OWES ADDITIONAL MONEY FOR BUILDING
 VALUATION AND RADON FEES.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved