2001-01-08 00:00:00 | CHECKLIST: |
| 1-EGRESS WINDOW IN BEDROOM #2 DOESN'T |
| COMPLY WITH SECTION 1005.4 SBC 1997. |
| 2-OPENINGS AT REAR ELEVATION EXCEED THE |
| PERCENTAGE ALLOWED BY TABLE 600 SBC/97 |
| CALCULATIONS ON SHEET A-8 ARE MISSING |
| THE SH H36 WINDOW BY BREAKFAST AREA. |
| ALSO, SEE WINDOW AND DOOR PRODUCT |
| APPROVAL FOR ACTUAL OPENING REQUIRED. |
| THOSE ARE THE RIGHT NUMBERS TO USE FOR |
| OPENING CALCULATIONS. |
| 3-UPDATE/REVISE ALL DRAWINGS AS REQUIRED |
| SEE COMMENTS ON PLANS.USE SBC 97 NO 99 |
| 4-ATTIC ACCESS TO BE 22"X36" MINIMUM. |
| SECTION 2309.6 SBC 1997. |
| 5-PRODUCT APPROVALS: |
| -PROVIDE COPIES OF TEST RESULTS FOR |
| SLIDING GLASS DOORS AS PER ASTM E 330. |
| SECTION 1706 SBC 1997. |
| -DRAWINGS FOR OUTSWING ENTRY DOOR WITH |
| LITES PRODUCT APPROVAL ARE NOT LEGIBLE |
| 6-STORM PANELS: |
| -REVISE KEY PLAN AND INSTALLATION SCHED |
| TO MATCH ARCHITECT'S PLAN ON SHEET A-8 |
| NOTE: WAIT TILL ARCHITECT REVISES PLAN |
| TO MEET THE TABLE 600 REQUIREMENTS. |
| -USE MASONRY ANCHOR SPACING WHEN PANELS |
| ARE TO BE ATTACHED TO MASONRY COLUMNS |
| WITH FILLED CELLS. |
| 7-FLOOD ZONE "AO". WILL NEED TO PROVIDE |
| ELEVATION CERTIFICATE. |
| 8-OWES ADDITIONAL MONEY FOR BUILDING |
| VALUATION AND RADON FEES. |