Plan Review Notes For Permit 00031492 |
Permit Number |
00031492 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ALL COMMON AREA TOILET ROOMS SHALL | | COMPLY W/FACBC SEC.4.22. | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | PER SPC SEC.501.7.SUPPLY PERMANENT FIXED | | LADDER OR RELOCATE EWH TO FLOOR. | | | | SUBMIT ELEVATION DETAILS FOR HANDICAP | | FIXTURES AND APPURTENANCES.MOUNTING | | HEIGHTS SHALL COMPLY W/FACBC. | | | | SUBMIT WATER SUPPLY RISER DIAGRAM FOR | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC. | | 104.2.1.WATER SUPPLY CONTROL SHALL | | COMPLY W/SPC 610.4.1,610.4.2 | | | | SINK IN LOUNGE SHALL COMPLY W/FACBC SEC. | | 4.24.1-4.24.7.CLEAR FLOOR SPACE SHALL BE | | CENTERED ON FIXTURE. | | | | SUBMIT OCCUPANT LOAD OF SPACE PER SPC | | SEC.407.1.3.SUPPLY MIN.FIXTURE REQS.PER | | TABLE 407 OF SPC. | | | | DRINKING FOUNTAINS ARE REQD.PER SPC | | TABLE 407.DRINKING FOUNTAINS SHALL | | COMPLY W/FACBC SEC.4.1.3.(10)(A). | | | | SHOWER SHALL COMPLY W/FACBC 4.21.2 THRU | | 4.21.8. |
|