Plan Review Notes For Permit 00031492 |
Permit Number |
00031492 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** PROVISO ************** | | | | 1)NOTE: NEED TO SHOW BRANCH CIRCUT #`S | | ON PLANS CORRESPONDING TO PANEL SCHEDULE | | 215-5 | | | | 2)NOTE: PLEASE LIST AIC RATING OF THE | | EQUIPMENT MAINS. MAINS ARE TO BE RATED | | FOR THE AVAILABLE FAULT CURRENT. 110-9 | | | | M)NOTE: YOU SHOW PANEL 'A' AS BEING MLO? | | IF THIS IS THE CASE THEN PLEASE SHOW THE | | EQUIPMENT GROUNDING CONDUCTOR REQ`D AND | | SIZE PER 250-122 | | | | 4)NOTE: YOU SHOW PANEL BEING INSTALLED | | IN CLOSET. THIS IS NOT PERMITTED! THIS | | AREA IS TO BE LABELED ON PLANS AS DED- | | -ICATED ELEC. EQUIPMENT SPACE/ROOM. | | PLEASE CHECK 384-7 AND 240-24D/110-26 | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEWBEFORE ANY ROUGH ELECTRICAL | | INSPECTION IS CALLED IN.IF THERE ARE ANY | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|