Plan Review Notes
Plan Review Notes For Permit 00031492
Permit Number 00031492
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: NEED TO SHOW BRANCH CIRCUT #`S
 ON PLANS CORRESPONDING TO PANEL SCHEDULE
 215-5
  
 2)NOTE: PLEASE LIST AIC RATING OF THE
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
  
 M)NOTE: YOU SHOW PANEL 'A' AS BEING MLO?
 IF THIS IS THE CASE THEN PLEASE SHOW THE
 EQUIPMENT GROUNDING CONDUCTOR REQ`D AND
 SIZE PER 250-122
  
 4)NOTE: YOU SHOW PANEL BEING INSTALLED
 IN CLOSET. THIS IS NOT PERMITTED! THIS
 AREA IS TO BE LABELED ON PLANS AS DED-
 -ICATED ELEC. EQUIPMENT SPACE/ROOM.
 PLEASE CHECK 384-7 AND 240-24D/110-26
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEWBEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372