Plan Review Notes
Plan Review Notes For Permit 00031388
Permit Number 00031388
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)FORM 600 A-97 OF ENERGY CODE LISTS
 3726 S.F.OF CONDITIONED FLOOR AREA AND
 SHEET C-1 OF PLANS LIST AREA UNDER AIR
 AS 3513 S.F.; CLARIFY
  
 2)SHEET A-5 SPECIFIES R-30 INSULATION
 AND ENERGY CALCULATIONS ARE BASED ON
 R-19 INSULATION,SEE EPL DISPLAY CARD;
 CLARIFY
  
 3)SHEET A-3 SHOWS MEAN ROOF HEIGHT OF
 +17'8",SHEET S-2 LISTS M.R.H.OF 15'-0",
 DESIGN COMPLIANCE FORM SHOWS 24" AND I
 CALCULATE IT TO BE +OR- 18'; CLARIFY
  
 4)SHEET S-3 STATES ASCE 7-93 WAS USED
 FOR CALCULATIONS, THE REFERENCED DESIGN
 STANDARD FOR USE WITH THE 97 SBC IS ASCE
 7-95, WHICH USES WIND LOADS IN EXCESS OF
 140 MPH.CLARIFY
  
 5)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR STORM
 PANELS
  
 6)PRODUCT APPROVALS FOR MULLIONS EXPIRED
 ON 5-1-00. PROVIDE 2 CURRENT COPIES.