2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE "AO". PROVIDE ELEVATION |
| CERTIFICATE AFTER SLAB IS POURED. |
| 2-PROVIDE PRODUCT APPROVAL FOR INSWING |
| ENTRY DOOR WITH SIDELITE ASSEMBLY AS |
| SHOWN ON ARCHITECT'S PLANS. |
| 3-ARCHITECT'S DRAWING D-2 SPECIFIES DADE |
| COUNTY PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS. INFORMATION SUBMITTED |
| DOESN'T HAVE A STANDARD PRODUCT |
| APPROVAL (AND PRODUCT APPROVAL THAT |
| WAS SUBMITTED HAS THE SEAL & SIGNATURE |
| OF ANOTHER ARCHITECT). REVISE DRAWING |
| OR RESUBMIT DADE COUNTY PRODUCT |
| APPROVAL. |
| |
| 4-12" GLASS BLOCK SPECIFIED DOESN'T MEET |
| THE ONE HOUR FIRE RATING. REVISE DWGS |
| |
| 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL |
| FOR CEILING CONSTRUCTION AT ENTRY AT |
| PORCH. SECTION 2504 SBC 1997. |
| 6-CLEARLY INDICATE HOW ARE OPENINGS |
| PREPARED TO RECEIVE STORM PANELS. |
| CLEARLY SPECIFY CONSTRUCTION OF THE |
| WINDOW SILL. THIS WILL DETERMINE THE |
| ACTUAL ANCHOR SPACING REQUIRED FOR THE |
| STORM PANELS. SEE PRODUCT APPROVAL. |
| 7-STORM PANELS: |
| -CLEARLY INDICATE/SPECIFY ANCHOR SCHED. |
| ACCORDING TO BUILDING STRUCTURE, STORM |
| PANEL SPAN AND EDGE DISTANCE. |
| NOTES: |
| A-THIS BUILDING IS MASONRY CONSTRUCT'N |
| CONCRETE VALUES MAY BE USED WHEN |
| ATTACHING TO PRECAST LINTELS OR PRE- |
| CAST OR POURED CONCRETE SILLS. |
| OTHERWISE USE MASONRY VALUES AS PER |
| PRODUCT APPROVAL. |
| 8-UPDATE/REVISE ALL DRAWINGS AS REQUIRED |
| SEE COMMENTS ON PLANS. |
| |
| |
| NOTE: STORM PANELS PRODUCT APPROVAL WILL |
| EXPIRE SOON. 6-26-00. MAKE SURE |
| TO OBTAIN UPDATED PRODUCT APPROVAL |
| FOR FUTURE APPLICATIONS TO AVOID |
| DELAYS. |