Plan Review Notes For Permit 00031237
Permit Number 00031237
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". WILL NEED ELEVATION
 CERTIFICATE.
 2-CLEARLY INDICATE ON PLANS GLAZING
 AREAS TO HAVE SAFETY GLAZING. SEE
 COMMENTS ON PLANS.
 SECTION 2405.2 SBC 1997.
 3-PROVIDE PRODUCT APPROVAL FOR OUTSWING
 ENTRY DOOR WITH SIDELITE ASSEMBLY.
 PLEASE MAKE SURE DRAWINGS ARE LEGIBLE.
 4-PROVIDE COPIES OF THE TEST RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM E-330.
 SECTION 1706 SBC 1997.
 5-STORM PANELS:
 -REVISE KEY PLAN AND INSTALLATION SCHED
 TO MATCH ARCHITECT'S PLAN ON SHEET A-8
 -USE MASONRY ANCHOR SPACING WHEN PANELS
 ARE TO BE ATTACHED TO MASONRY COLUMNS
 WITH FILLED CELLS.
 6-UPDATE ALL DRAWINGS. SEE COMMENTS ON
 PLANS.