Plan Review Notes For Permit 00031237 |
Permit Number |
00031237 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE "AO". WILL NEED ELEVATION | | CERTIFICATE. | | 2-CLEARLY INDICATE ON PLANS GLAZING | | AREAS TO HAVE SAFETY GLAZING. SEE | | COMMENTS ON PLANS. | | SECTION 2405.2 SBC 1997. | | 3-PROVIDE PRODUCT APPROVAL FOR OUTSWING | | ENTRY DOOR WITH SIDELITE ASSEMBLY. | | PLEASE MAKE SURE DRAWINGS ARE LEGIBLE. | | 4-PROVIDE COPIES OF THE TEST RESULTS FOR | | SLIDING GLASS DOORS AS PER ASTM E-330. | | SECTION 1706 SBC 1997. | | 5-STORM PANELS: | | -REVISE KEY PLAN AND INSTALLATION SCHED | | TO MATCH ARCHITECT'S PLAN ON SHEET A-8 | | -USE MASONRY ANCHOR SPACING WHEN PANELS | | ARE TO BE ATTACHED TO MASONRY COLUMNS | | WITH FILLED CELLS. | | 6-UPDATE ALL DRAWINGS. SEE COMMENTS ON | | PLANS. |
|