Plan Review Notes
Plan Review Notes For Permit 00030941
Permit Number 00030941
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SQUARE FOOTAGE OF BUILDING PER
 SPC SEC.407.1.3.FOR MIN.PLUMBING REQS.
  
 SINK IN LOUNGE /KITCHEN SHALL COMPLY W/
 FACBC SEC.4.24.1-4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 1ST.
 AND SECOND FLOORS PER TABLE 407 OF SPC.
  
 SUBMIT ELEVATION DETAILS FOR ALL HANDI-
 CAP FIXTURES AND APPURTENANCES.
  
 SUBMIT OCCUPANT LOAD OF 2ND. FLR.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 TOILET ROOM ON 2ND.FLR.SHALL COMPLY W/
 FACBC SEC.4.1.6.(B),
  
 CLEARLY SHOW SHOWER DIMENSIONS.COMPLY W/
 FACBC SEC.4.1.3(11),4.21,4.23
  
 SIZE OF TOILET ROOM ON 2ND.SHALL COMPLY
 W/FACBC SEC.4.2.3,4.16.2.
  
 SUBMIT SANITARY AND WATER SUPPLY RISERS
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
  
 THIS IS A CHANGE OF OCCUPANCY AND BLDG.
 SHALL COMPLY W/FACBC 4.1.6 FOR VERTICAL
 ACCESSIBILITY OR SUBMIT WAIVER FROM FLA
 DEPT.OF COMMUNITY AFFAIRS NOT REQUIRING
 VERTICAL ACCESSIBILITY.