2001-01-08 00:00:001]PLEASE CLERIFY TYPE OF CONSTRUCTION
 AND IF THE BUILDING IS SPRINKLED.
 2]SUBMIT AN EXITING PLAN,IDENTIFYING TWO
 APPROVED EXITS COMPLYING WITH SECTIONS
 1004.2 AND 1004.3 SBC [CANNOT EXIT
 THRU PARTS ROOM OR RESTROOMS]
 3]EXPLAIN AREAS NOT IN USE,THEY MAY BE
 REQUIRED TO HAVE FIRE SEPERATION
 4]TABLE 704.1,SBC,REQUIRES OCCUPANCY
 SEPERATION BETWEEN SERVICE AREA AND
 BUISNESS USE.
 5]SECTION 7.2 FL.ACC.CODE REQUIRES
 SERVICE COUNTERS TO BE ACCESSIBLE
 [PARTS ROOM]
 6]SECTION 4.13.6,FAC,DOOR SEPERATING NEW
 CORRIDOR AND EXISTING CORRIDOR DOES
 NOT COMPLY.
 7]CASHIER/CUSTOMER AREA MUST COMPLY WITH
 1997 FAC
 8]CONSTRUCTION VALUE SUBMITTED SEEMS LOW
 PLEASE PROVIDE COPY OF SIGNED CONTRACT