Plan Review Notes
Plan Review Notes For Permit 00030757
Permit Number 00030757
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:ALL PLANS NEED TO HAVE AIC RATING
 SUBMITTED ON PLANS.110-09/215-5
 MAINS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE LIST THE REQ`D CIRCUIT
 FOR BATH(S) AS PER 210-11-C-3/215-5
  
 4)NOTE: ALL SERVICE ENTRANCE CONDUCTORS
 ARE TOO SMALL FOR SERVICE AND LOAD.
 310-16 PLEASE CORRECT.
  
 5)NOTE: AS REQ`D BY 250-50 GROUNDING
 ELECTRODE CONDUCTOR MUST GO TO BLDG
 STEEL. PLEASE SHOW.
  
 6)NOTE: AS PER 210-52E GFI IN FRONT OF
 DWELLING IS REQ`D. PLEASE SHOW.
  
 7)NOTE: NEED TO HAVE GFI RECEPT FOR A/C
 AS PER 210-63
  
 ALL THE ABOVE NOTES HAVE BEEN GIVEN AS
 PREVIOUS NOTES. ALL THE ABOVE NEEDS TO
 BE ON ALL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372