Plan Review Notes For Permit 00030757 |
Permit Number |
00030757 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE:ALL PLANS NEED TO HAVE AIC RATING | | SUBMITTED ON PLANS.110-09/215-5 | | MAINS ARE TO BE RATED FOR THE AVAILABLE | | FAULT CURRENT. | | | | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1 | | | | 3)NOTE: PLEASE LIST THE REQ`D CIRCUIT | | FOR BATH(S) AS PER 210-11-C-3/215-5 | | | | 4)NOTE: ALL SERVICE ENTRANCE CONDUCTORS | | ARE TOO SMALL FOR SERVICE AND LOAD. | | 310-16 PLEASE CORRECT. | | | | 5)NOTE: AS REQ`D BY 250-50 GROUNDING | | ELECTRODE CONDUCTOR MUST GO TO BLDG | | STEEL. PLEASE SHOW. | | | | 6)NOTE: AS PER 210-52E GFI IN FRONT OF | | DWELLING IS REQ`D. PLEASE SHOW. | | | | 7)NOTE: NEED TO HAVE GFI RECEPT FOR A/C | | AS PER 210-63 | | | | ALL THE ABOVE NOTES HAVE BEEN GIVEN AS | | PREVIOUS NOTES. ALL THE ABOVE NEEDS TO | | BE ON ALL PLANS. | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|