2001-01-08 00:00:00**************** UNSAT ****************
  
 1) NOTE: NEED TO SUBMIT THE AIC RATING
 FOR EQUIPMENT MAINS!!! 110-9/215-5
 THIS WILL BE REQ`D ON ALL PLANS.
  
 2)NOTE: ALSO PLEASE LIST THE REQ`D BATH-
 CIRCUIT(S) AS REQ`D BY 210-11-C-3
 PLEASE LIST ON PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372