Plan Review Notes For Permit 00030350 |
Permit Number |
00030350 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE:PLEASE INDICATE ON PLANS WHAT | | ELECTRICAL IS EXISTING AND NEW? OUTLETS | | ETC. | | | | 2)NOTE: PLEASE INDICATE ROOF TOP GFI | | OUTLET FOR A/C UNITS. 210-63 | | | | 3)NOTE:PLEASE NOTE THE REQ`D OUTLETS | | FOR SHOW WINDOW LIGHTING. 210-62 | | | | 4)NOTE:PLEASE INDICATE ON PLANS THE | | BRANCH CIRCUT #`S FOR ALL CIRCUTS. 215-5 | | | | 5)NOTE: PLEASE GIVE MORE DETAIL ON THE | | GROUNDING ELECTRODE SYSTEM. YOU SHOW | | GOING TO CU PIPE ONLY. NOTE ART 250 | | | | 6)NOTE: NEED TO SUBMIT THE AIC RATING | | OF EQUIPMENT MAINS. PER 110-9/110-10 / | | 215-5. MAINS ARE TO BE RATED FOR THE | | AVAILABLE FAULT CURRENT. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW AND APPROVAL. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 | | EXT 8372 |
|