Plan Review Notes
Plan Review Notes For Permit 00030350
Permit Number 00030350
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE:PLEASE INDICATE ON PLANS WHAT
 ELECTRICAL IS EXISTING AND NEW? OUTLETS
 ETC.
  
 2)NOTE: PLEASE INDICATE ROOF TOP GFI
 OUTLET FOR A/C UNITS. 210-63
  
 3)NOTE:PLEASE NOTE THE REQ`D OUTLETS
 FOR SHOW WINDOW LIGHTING. 210-62
  
 4)NOTE:PLEASE INDICATE ON PLANS THE
 BRANCH CIRCUT #`S FOR ALL CIRCUTS. 215-5
  
 5)NOTE: PLEASE GIVE MORE DETAIL ON THE
 GROUNDING ELECTRODE SYSTEM. YOU SHOW
 GOING TO CU PIPE ONLY. NOTE ART 250
  
 6)NOTE: NEED TO SUBMIT THE AIC RATING
 OF EQUIPMENT MAINS. PER 110-9/110-10 /
 215-5. MAINS ARE TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372