Plan Review Notes For Permit 00030144 |
Permit Number |
00030144 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ******************* UNSAT ************* | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | MAINS> 110-9 | | | | 2)NOTE: SHEET #1 SHOWS MAIN DISC AND | | PANEL? SHEET #2 SHOWS ONLY MB PANEL? | | PLEASE CORRELATE RISER DIAGRAMS. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D DEDICATED | | CIRCUT(S) FOR BATH(S) PER 210-11-C-3 | | #12 AND 20 AMP | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|