Date |
Text |
2001-01-08 00:00:00 | 1)IRRIGATION PLANS SHAL BE SIGNED AND |
| SEALED IF VALUE IS OVER $50,000 PER F.S. |
| 553.79. |
| |
| 2)ARCHITECTURAL PLANS SHALL BE SIGNED |
| AND DATED.(PLANS ARE SEALED.)PER FLA. |
| STATUTE 481.221. |
| |
| 3)A WATER USE PERMIT IS REQD.FROM SFWMD |
| FOR THE IRRIGATION SYSTEM.FLA.STATUTE |
| 373.219. |
| |
| |
| 4)SIZE OF GREASE TRAP SHALL BE APPROVED |
| BY CITY OF WPB UTILITIES.CONTACT RODNEY |
| COMPO AT 561-835-7423.SUBMIT COPY OF |
| APPROVAL FORM. |
| |
| 5)SANITARY SYSTEM REQUIRES ONE MAIN VENT |
| THROUGH THE ROOF PER SPC SEC.904.3.1. |
| |
| 6)CALCULATIONS FOR COMBUSTION AIR SHALL |
| BE ON THE PLANS.PROVISIONS SHALL BE MADE |
| FOR FUTURE DRYER.SGC.SEC.402.4.4.4,NFPA |
| 54 SEC.5.3.5. |
| |
| 7)SUBMIT DETAIL OF LINT INTERCEPTOR. |
| COMPLY W/SPC 1004.10.1.1. |
| |
| 8)FLOOR DRAINS ARE REQD.IN THE LAUNDRY |
| ROOM PER SPC SEC.409.4.5. |
| |
| 9)SHT.P4.2-MIN.SIZE VENT SHALL BE 3"PER |
| SPC SEC.911.3,TABLE 911.3.SEE RISER "D". |
| |
| 10)APPROVAL FROM DEPT.OF BUSINESS REG. |
| REQD.PRIOR TO APPROVAL FROM THIS DEPT. |
| COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 |
| |
| 11)DESIGN OF WASTE FOR KITCHEN SHALL |
| COMPLY W/SPC SEC.921 FOR HORIZ.WASTE AND |
| VENT SYSTEM. |
| |
| 12)ALL RISERS ARE SHOWN WITH FLAT DRY |
| MAIN VENTS.COMPLY W/SPC SEC.906.2.1. |
| |
| 13)DELETED.8/13/00.TKL. |
| |
| 14)DRAINS AT TRENCH DRAIN SHALL BE |
| EQUIPPED W/AIR GAPS PER SPC SEC.806. |
| |
| 15)CONTACT R.COMPO AT 561-835-7423 FOR |
| APPROVAL OF OIL INTERCEPTOR. |
| |
| |
| 16)TWO WAY CLEANOUTS ARE REQD.ON THE |
| INLET AND OUTLET OF THE GREASE INTER- |
| CEPTOR.SPC 710.4.SEE ATTACHED. |
| |
| 17)THE MIN.NUMBER OF PLUMBING FIXTURES |
| FOR THE POOL SHALL COMPLY W/FLA.DEPT.OF |
| HEALTH CHAPTER 64E-9.IF POOL AND POOL |
| BUILDING WILL BE PERMITTED SEPARATELY, |
| NOTE SUCH ON THE PLANS.. |
| |
| CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| ANY QUESTIONS. |
| TIMOTHY LARGE |
| PLUMBING PLANS EXAMINER. |