Date |
Text |
2001-01-08 00:00:00 | SUBMIT A COMPLETE SET OF PLUMBING |
| DRAWINGS FOR REVIEW.COUNTYWIDE AMEND- |
| MENTS TO SPC SEC.104.2.1.(INCLUDE CON- |
| DENSATE RISER AND WATER RISERS.) |
| |
| SUBMIT A COMPLETE GAS ISOMETRIC FOR |
| REVIEW. SHOW TYPE OF PIPING,ALL CUT |
| SECTIONS OF PIPE,DISTANCE TO MOST REMOTE |
| OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL |
| BTU LOAD ON THE SYSTEM.SUBMIT COPY OF/OR |
| REFERENCE APPLICABLE SIZING TABLE USED |
| IN SYSTEM DESIGN,SHOW LOCATION OF METER. |
| |
| OIL INTERCEPTOR DESIGN SHALL COMPLY W/ |
| CITY OF WEST PALM BEACH DEPT.OF |
| ENGINEERING STANDARDS. |
| |
| SANITARY SYSTEM REQUIRES ONE MAIN VENT |
| THROUGH ROOF.(THIS IS NOT CLEARLY SHOWN |
| ON THE PLANS.)SPC SEC.904.3.1. |
| |
| WASTE STACKS SHALL COMPLY W/SPC SEC. |
| 714.2.(SEE STACK"B" AND CHECK ALL OTHER |
| STACKS). |
| |
| DESIGN AND CAPACITY OF GREASE TRAP SHALL |
| BE APPROVED BY THE CITY OF WEST PALM |
| BEACH UTILITIES.CONTACT R.COMPO AT |
| 561-835-7423.SUBMIT COPY OF APPROVAL |
| FORM FROM UTILITIES. |
| |
| SUBMIT CALCULATIONS FOR COMBUSTION AIR |
| FOR ALL GAS EQUIPMENT.COMPLY W/SGC SEC. |
| 402.4.` |
| |
| A LINT INTERCEPTOR IS REQUIRED FOR THE |
| WASHING MACHINES LOCATED IN THE LAUNDRY |
| ROOMS.SUBMIT DETAIL OF INTERCEPTOR. |
| COMPLY W/SPC SEC.1004.10.1.1.AND FLOOR |
| DRAINS ARE REQD.IN THE LAUNDRY ROOMS PER |
| SPC SEC.409.4.5. |
| |
| TWO WAY CLEANOUTS ARE REQD.ON THE INLET |
| AND OUTLET LINES OF THE INTERCEPTORS PER |
| SPC 710.4. |
| |
| VACUUM RELIEF VALVES ARE REQUIRED ON THE |
| WATER HEATERS AND STORAGE TANK PER SPC |
| SEC.507.1.2. |
| |
| SHT.4.2-RISER "D"-MIN.SIZE VENT SHALL BE |
| 3"PER SPC SEC.911.3,TABLE 911.3. |
| |
| INDICATE SLOPE OF PIPE ON PLANS.COMPLY |
| W/TABLE 714.1,714.2. |
| |
| WHIRLPOOL TUBS IN ROOMS 105,107 NOT |
| PROPERLY VENTED.SPC SEC.901.2. |
| |
| SHT.P4.3-LAYOUT OF RISER DIAGRAM DOESN'T |
| CORRELATE W/SHT.P2.1.(SEE 4"SAN.BY |
| TOILET ROOMS.) |
| |
| WHERE IS APPROVAL FROM DEPT.OF BUSINESS |
| AND PROFESSIONAL REGULATION FOR |
| RESTAURANT? SUBMIT COPY OF APPROVAL. |
| COUNTYWIDE AMENDMENT TO SPC SEC.101.4.7. |
| |
| IF YOU HAVE ANY QUESTIONS I CAN BE |
| REACHED AT 561-659-8096,EXT.8377. |