Plan Review Notes For Permit 00030112 |
Permit Number |
00030112 |
|
Review Stop |
FIRE |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1. PROVIDE TAMPER SWITCHES ON DOUBLE | | DETECTOR CHECK VALVES. | | 2.FIRE ALARM SYSTEM SHALL BE CLASS "A" | | OR ADDRESSABLE. | | 3.FIRE ALARM SYSTEM SHALL BE 15 DECIBELS | | ABOVE AMBIENT NOISE THROUGHOUT. | | 4. PROVIDE FIRE ALARM STROBE LIGHTS IN | | ALL PUBLIC RESTROOMS. | | 5. PROVIDE APPROVED DOOR CLOSERS ON ALL | | RATED FIRE DOORS. | | 6. PROVIDE APPROVED WIRED-IN SMOKE | | DETECTORS IN ALL GUESTROOMS. |
|