2001-01-08 00:00:001)PLANS SHALL BE APPROVED BY CITY OF
 WEST PALM BEACH ENGINEERING DEPT.FOR THE
 WATER SEWER,AND STORM DRAINAGE.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 2)SUBMIT COPIESOF APPROVALS FROM P.B.
 COUNTY HEALTH DEPT.AND DEP,(NOT INCLUDED
 W/RESPONSE SHEET.)COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7
  
 3)FLOOR DRAINS SHALL BE INSTALLED SO
 INLET IS AT ALL TIMES IN FULL VIEW.SEE
 F.D.IN 1ST.FLR.VENDING AREA.SPC SEC.
 409.4.1.2.
  
 4)SUBMIT COMPLETE GAS ISOMETRIC FOR
 REVIEW.SHOW TYPE OF PIPING,ALL CUT
 SECTIONS OF PIPE,DISTANCE TO MOST REMOTE
 OUTLET,BTU LOAD OF EACH APPLIANCE,TOTAL
 LOAD ON SYSTEM.SUBMITAPPLICABLE
 SIZING TABLE USED T0 DESIGN THE SYSTEM.
  
 5)SUBMIT DETAIL OF OIL INTERCEPTOR FOR
 ELEVATOR SUMP AND PUMP.VENTS SHALL
 COMPLY W/SPC SEC.906.2.1.
  
 6)SANITARY SYSTEM REQUIRES ONE MAIN VENT
 THROUGH THE ROOF.(DOES NOT APPEAR TO BE
 ON THE PLANS.)
  
 7)SHT.P-4-VENTS FOR TUBS SHALL COMPLY W/
 SPC SEC.906.2.1.(THEY SHALL BE A MIN.OF
 6"ABOVE THE FLOOD LEVEL RIM OF THE
 FIXTURE BEFORE OFFSETTING HORIZONTALLY.)
  
 8)VENT STACKS FOR WASTE AND SOIL STACKS
 SHALL COMPLY W/SPC 906.2.2, 918.
  
 9)KITCHEN STACK DIAGRAM-FIXTURES SHALL
 DISCHARGE TO GREASY WASTE,NOT TO
 SANITARY PER SPC SEC.1004.1, 1004.4.
 DRY VENTS NOT PERMITTED.
  
 10)SHT.P-4.3-TUBS,W.C.'S AND SHOWERS
 SHALL COMPLY W/SPC SEC.906.2.2.(VENTS)
  
 11)DESIGNAND CAPACITY OF GREASE TRAP
 SHALL BE APPROVED BY CITY OF WEST PALM
 UTILITIES.CALL R.COMPO AT (561)835-7423
 SUBMIT COPY OF APPROVAL FORM FROM
 UTILITIES.
  
 12)DESIGN OF CONDENSATE SYSTEM SHALL
 COMPLY W/SPC 304.8.3,304.8.4. OF SMC.
  
 13)SUBMIT DETAILS ON GAS VENTS.SHOW
 TERMINATION POINTS.COMPLY W/SGC SEC.
 608.
  
 14)SIZING OF BRANCH VENT FOR 1ST.FLR.
 TOILET ROOM SHALL COMPLY W/SPC TABLE
 920.4.
  
 15)ALL ADDENDUMS SHALL BE DRAWN ON FULL
 SHEETS AND SIGNED AND SEALED PER FLA.
 STATUTE.
  
 16)A LINT INTERCEPTOR IS REQUIRED FOR
 THE DISCHARGE FROM THE LAUNDRY ROOMS.SPC
 SEC.1004.11
  
 17)THE GREASE TRAP SHALL COMPLY W/
 CITY OF WEST PALM BEACH UTILITIES.
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET DRAIN LINES,AND MANHOLES ARE
 REQD.ON THE INLET AND OUTLET.
  
 18)WATER SUPPLY BRANCHES TO THE ROOMS
 SHALL BE VALVED PER SPC SEC.610.4.1.
  
 19)A WELL DRILLING PERMIT IS REQD.FROM
 DEP FOR THE WELL AND A WATER USE PERMIT
 IS REQD. FROM SFWMD FOR THE IRRIGATION
 SYSTEM PER FLA.STATUTE 373.219.