Date |
Text |
2001-01-08 00:00:00 | CONTINUATION OF PLUMBING PLAN REVIEW: |
| SHT.P-1.1.-MIN.SIZE OF WASHING MACHINE |
| DRAIN AND STANDPIPE SHALL BE 2" PER SPC |
| TABLE 713.1. |
| |
| SHT.P-2.1-FLOOR DRAIN IN LAUNDRY ROOM |
| #112 SHALL BE IN FULL VIEW PER SPC |
| 409.4.1.2. |
| |
| DISCHARGE OF SUMP PUMP SHALL BE TO |
| SANITARY SYSTEM,NOT TO STORM AND SHALL |
| DISCHARGE THROUGH AN INTERCEPTOR PER |
| SPC SEC.1004.1. |
| |
| RELIEF LINES FROM WATER HEATERS SHALL |
| DISCHARGE TO EXTERIOR PER COUNTYWIDE |
| AMENDMENTS TO SPC SEC.507.6(3).SEE JOB |
| SPEC.15486-3.02(F). |
| |
| SHT.P-3.3.-SHOWS SANITARY TO GREASE INT. |
| COMPLY W/SPC SEC.1004.3. |
| |
| SHT.P-4.1-WATER RISER #4 DOESN'T MATCH |
| FLOOR PLAN ON P-2.2. |
| |
| WATER SUPPLY CONTROL FOR RISERS AND |
| BRANCHES SHALL COMPLY W/SPC SEC.610.4.1, |
| 610.4.2. |
| |
| SUBMIT WATER RISER DIAGRAMS FOR ALL |
| AREAS.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| 104.2.1. |
| |
| SANITARY SYSTEM REQS.ONE MAIN VENT THRU |
| ROOF PER SPC SEC.904.3.1.SHOW TERM- |
| INATION POINT OF ALL VENTS. |
| |
| SHT.P-4.2-VENTS FOR TUBS SHALL COMPLY W/ |
| SPC SEC.906.2.1.(SEE RISER "C"-DOESN'T |
| MATCH FLOOR PLAN.) |
| |
| VENT STACKS FOR WASTE AND SOIL STACKS |
| SHALL COMPLY W/SPC SEC.906.2.2,918. |
| DRY VENTS NOT PERMITTED. |
| |
| SHT.P-4.2-KIT.STACK DIAGRAM-FIXTURES |
| SHALL DISCHARGE TO GREASY WASTE,NOT TO |
| SANITARY PER SPC SEC.1004.1,1004.4. |
| DRY VENTS NOT PERMITTED. |
| |
| VENTS FOR FLOOR DRAINS SHALL COMPLY W/ |
| SPC SEC.904.2.1. |
| |
| SHT.P-4.3-VENTS FOR TUBS,W.C.'S,SHOWERS |
| SHALL COMPLY W/SPC SEC.906.2.2. |
| |
| ANTI-SCALD VALVES ARE REQD.IN SHOWERS |
| PER SPC SEC.613.1. |
| |
| DESIGN AND CAPACITY OF GREASE TRAP SHALL |
| COMPLY W/CITY OF WPB UTILITIES REQS. |
| CONTACT RODNEY COMPO AT (561)835-7423. |
| SUBMIT APPROVAL FORM FROM UTILITIES DEPT |
| |
| SIZING OF CONDENSATE DRAINS FROM PTAC |
| UNITS SHALL COMPLY W/SMC SEC.304.8.4. |
| (SEE SHT.M-3.1.) |
| |
| SUBMIT DETAILS ON VENTS FOR GAS EQUIP. |
| TERMINATION OF GAS VENTS SHALL COMPLY W/ |
| SGC SEC.608,609 |
| |
| END OF COMMENTS. |
| TIMOTHY LARGE-PLUMBING PLANS EXAMINER |
| (561)659-8096,EXT.8377. |
| |
| SIZING OF BRANCH VENT FOR 1ST.FLR.TOILET |
| ROOMS SHALL COMPLY W/SPC TABLE 920.4. |