Plan Review Notes
Plan Review Notes For Permit 00030112
Permit Number 00030112
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CONTINUATION OF PLUMBING PLAN REVIEW:
 SHT.P-1.1.-MIN.SIZE OF WASHING MACHINE
 DRAIN AND STANDPIPE SHALL BE 2" PER SPC
 TABLE 713.1.
  
 SHT.P-2.1-FLOOR DRAIN IN LAUNDRY ROOM
 #112 SHALL BE IN FULL VIEW PER SPC
 409.4.1.2.
  
 DISCHARGE OF SUMP PUMP SHALL BE TO
 SANITARY SYSTEM,NOT TO STORM AND SHALL
 DISCHARGE THROUGH AN INTERCEPTOR PER
 SPC SEC.1004.1.
  
 RELIEF LINES FROM WATER HEATERS SHALL
 DISCHARGE TO EXTERIOR PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6(3).SEE JOB
 SPEC.15486-3.02(F).
  
 SHT.P-3.3.-SHOWS SANITARY TO GREASE INT.
 COMPLY W/SPC SEC.1004.3.
  
 SHT.P-4.1-WATER RISER #4 DOESN'T MATCH
 FLOOR PLAN ON P-2.2.
  
 WATER SUPPLY CONTROL FOR RISERS AND
 BRANCHES SHALL COMPLY W/SPC SEC.610.4.1,
 610.4.2.
  
 SUBMIT WATER RISER DIAGRAMS FOR ALL
 AREAS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SANITARY SYSTEM REQS.ONE MAIN VENT THRU
 ROOF PER SPC SEC.904.3.1.SHOW TERM-
 INATION POINT OF ALL VENTS.
  
 SHT.P-4.2-VENTS FOR TUBS SHALL COMPLY W/
 SPC SEC.906.2.1.(SEE RISER "C"-DOESN'T
 MATCH FLOOR PLAN.)
  
 VENT STACKS FOR WASTE AND SOIL STACKS
 SHALL COMPLY W/SPC SEC.906.2.2,918.
 DRY VENTS NOT PERMITTED.
  
 SHT.P-4.2-KIT.STACK DIAGRAM-FIXTURES
 SHALL DISCHARGE TO GREASY WASTE,NOT TO
 SANITARY PER SPC SEC.1004.1,1004.4.
 DRY VENTS NOT PERMITTED.
  
 VENTS FOR FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.904.2.1.
  
 SHT.P-4.3-VENTS FOR TUBS,W.C.'S,SHOWERS
 SHALL COMPLY W/SPC SEC.906.2.2.
  
 ANTI-SCALD VALVES ARE REQD.IN SHOWERS
 PER SPC SEC.613.1.
  
 DESIGN AND CAPACITY OF GREASE TRAP SHALL
 COMPLY W/CITY OF WPB UTILITIES REQS.
 CONTACT RODNEY COMPO AT (561)835-7423.
 SUBMIT APPROVAL FORM FROM UTILITIES DEPT
  
 SIZING OF CONDENSATE DRAINS FROM PTAC
 UNITS SHALL COMPLY W/SMC SEC.304.8.4.
 (SEE SHT.M-3.1.)
  
 SUBMIT DETAILS ON VENTS FOR GAS EQUIP.
 TERMINATION OF GAS VENTS SHALL COMPLY W/
 SGC SEC.608,609
  
 END OF COMMENTS.
 TIMOTHY LARGE-PLUMBING PLANS EXAMINER
 (561)659-8096,EXT.8377.
  
 SIZING OF BRANCH VENT FOR 1ST.FLR.TOILET
 ROOMS SHALL COMPLY W/SPC TABLE 920.4.