Notes
Date Text
2001-01-08 00:00:00SHOW WATER SOURCE FOR IRRIGATION SYSTEM.
 IF FROM A WELL OR ARTIFICIAL BODY OF
 WATER A WATER USE PERMIT WILL BE REQD.
 FROM SO.FLA.WATER MNGMT.DISTRICT PER
 FLA.STATUTE 373.219.
  
 A RAIN SENSOR AND CONTROLLER SHALL BE
 INSTALLED ON THE IRRIGATION SYSTEM PER
 FLA.STATUTE SEC.373.62.
  
 CIVIL PLANS SHALL BE APPROVED BY CITY OF
 WEST PALM BEACH ENGINEERING DEPT.FOR THE
 WATER,SEWER AND STORM DRAINAGE.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 SUBMIT COPIES OF APPROVALS FROM DEP AND
 HEALTH DEPT.FOR INSTALLATION OF WATER
 MAIN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 PLANS SHALL BE ROUTED TO THE DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 SPEC.15140-PART 3.09(E).-HORIZONTAL
 COPPER PIPING SHALL BE SUPPORTED PER
 SPC SEC.310.3.4.
  
 SPEC.15430-3.01(G)-SPACING AND SIZE OF
 CLEANOUTS IN THE DRAINAGE SYSTEM SHALL
 COMPLY W/ SPC SEC.710.2.4.(1)(2),711.
  
 SPEC.15430-3.01(T)-TWOWAY CLEANOUTS
 ARE REQD.ON THE INLET AND OUTLET OF THE
 GREASE TRAP PER SPC 710.4.
  
 SHOW WIDTH AND LENGTH OF STANDARD SHOWER
 AND HANDICAP SHOWER STALLS.COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC,
 409.8.2.1.,FACBC SEC.4.21.2 - 4.21.8.
 FIG.57,(A) OR (B).
  
 SHT.A-3.6-SHOW FIXTURE CLEARANCE OF
 WATER CLOSETS IN ACCESSIBLE BATHROOMS.
  
 GRAB BARS IN SLEEPING UNITS SHALL COMPLY
 W/FACBC SEC.4.26 & FIGS.33 & 34.VERTICAL
 BARS NOT ACCEPTABLE.SEE SHT.A-3.9.
  
 EQUIVALENT FACILITATION SHALL BE
 PROVIDED PER FACBC SEC.9.1.4.
 ACCESSIBLE ROOMS SHALL BE EVENLY DIS-
 PERSED.
  
 TOILETS IN ALL ACCESSIBLE ROOMS SHALL BE
 PROVIDED W/A PORTABLE OR ATTACHED SEAT
 PER FACBC SEC.9.2.3.
  
 KITCHENS,KITCHENETTES,OR WET BARS IN
 SLEEPING UNITS SHALL COMPLY W/FACBC SEC.
 9.2.2.(7)
  
 SHT.A-4.1-FLOOR DRAIN SHOWN UNDER ICE
 MACHINE-INLET SHALL BE IN FULL VIEW PER
 SPC SEC.409.4.1.2.
  
 SHT.A-8.4-DETAIL #6-CLEAR FLOOR SPACE
 SHALL BE PROVIDED FOR SINK AND SHALL BE
 CENTERED ON THE FIXTURE AND COMPLY W/
 FACBC SEC.4.24.1-4.24.7.
  
 GUEST LAUNDRY SHALL COMPLY W/FACBC SEC.
 9.1.1.
  
 WALLS AND FLOOR IN EMPLOYEE TOILET SHALL
 BE NONABSORBENT TO A HEIGHT OF 4' PER
 SBC SEC.1204.2.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 EQUIPMENT SHALL BE LISTED PER SGC SEC.
 402.1
  
 SUBMIT COMPLETE GAS DRAWING FOR REVIEW.
 SHOW TYPE OF PIPING,SIZES,BTU RATING OF
 EACH APPLIANCE,ETC.COMPLY W/SGC CHAPTS.
 3-6 & NFPA 54,58.INCLUDE CALCULATIONS
 FOR COMBUSTION AIR.
  
 MAX.TEMP.TO PUBLIC RESTROOMS SHALL NOT
 EXCEED 110 DEG.PER FLA.ENERGY CODE SEC.
 412.1.ABCD.2.3.2.
  
 SHT.P-1.1.-REMOVE VACUUM BREAKERS FROM
 WASHING MACHINE.
  
 SEE PLUMBING PLAN REVIEW STEP #2 FOR
 CONTINUATION OF PLUMBING COMMENTS.