2001-01-08 00:00:00 | SHOW WATER SOURCE FOR IRRIGATION SYSTEM. |
| IF FROM A WELL OR ARTIFICIAL BODY OF |
| WATER A WATER USE PERMIT WILL BE REQD. |
| FROM SO.FLA.WATER MNGMT.DISTRICT PER |
| FLA.STATUTE 373.219. |
| |
| A RAIN SENSOR AND CONTROLLER SHALL BE |
| INSTALLED ON THE IRRIGATION SYSTEM PER |
| FLA.STATUTE SEC.373.62. |
| |
| CIVIL PLANS SHALL BE APPROVED BY CITY OF |
| WEST PALM BEACH ENGINEERING DEPT.FOR THE |
| WATER,SEWER AND STORM DRAINAGE.COUNTY- |
| WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| |
| SUBMIT COPIES OF APPROVALS FROM DEP AND |
| HEALTH DEPT.FOR INSTALLATION OF WATER |
| MAIN.COUNTYWIDE AMENDMENTS TO SPC SEC. |
| 101.4.7. |
| |
| PLANS SHALL BE ROUTED TO THE DEPT.OF |
| BUSINESS REGULATION FOR REVIEW AND |
| APPROVAL.COUNTYWIDE AMENDMENTS TO SPC |
| SEC.101.4.7. |
| |
| SPEC.15140-PART 3.09(E).-HORIZONTAL |
| COPPER PIPING SHALL BE SUPPORTED PER |
| SPC SEC.310.3.4. |
| |
| SPEC.15430-3.01(G)-SPACING AND SIZE OF |
| CLEANOUTS IN THE DRAINAGE SYSTEM SHALL |
| COMPLY W/ SPC SEC.710.2.4.(1)(2),711. |
| |
| SPEC.15430-3.01(T)-TWOWAY CLEANOUTS |
| ARE REQD.ON THE INLET AND OUTLET OF THE |
| GREASE TRAP PER SPC 710.4. |
| |
| SHOW WIDTH AND LENGTH OF STANDARD SHOWER |
| AND HANDICAP SHOWER STALLS.COMPLY W/ |
| COUNTYWIDE AMENDMENTS TO SPC SEC, |
| 409.8.2.1.,FACBC SEC.4.21.2 - 4.21.8. |
| FIG.57,(A) OR (B). |
| |
| SHT.A-3.6-SHOW FIXTURE CLEARANCE OF |
| WATER CLOSETS IN ACCESSIBLE BATHROOMS. |
| |
| GRAB BARS IN SLEEPING UNITS SHALL COMPLY |
| W/FACBC SEC.4.26 & FIGS.33 & 34.VERTICAL |
| BARS NOT ACCEPTABLE.SEE SHT.A-3.9. |
| |
| EQUIVALENT FACILITATION SHALL BE |
| PROVIDED PER FACBC SEC.9.1.4. |
| ACCESSIBLE ROOMS SHALL BE EVENLY DIS- |
| PERSED. |
| |
| TOILETS IN ALL ACCESSIBLE ROOMS SHALL BE |
| PROVIDED W/A PORTABLE OR ATTACHED SEAT |
| PER FACBC SEC.9.2.3. |
| |
| KITCHENS,KITCHENETTES,OR WET BARS IN |
| SLEEPING UNITS SHALL COMPLY W/FACBC SEC. |
| 9.2.2.(7) |
| |
| SHT.A-4.1-FLOOR DRAIN SHOWN UNDER ICE |
| MACHINE-INLET SHALL BE IN FULL VIEW PER |
| SPC SEC.409.4.1.2. |
| |
| SHT.A-8.4-DETAIL #6-CLEAR FLOOR SPACE |
| SHALL BE PROVIDED FOR SINK AND SHALL BE |
| CENTERED ON THE FIXTURE AND COMPLY W/ |
| FACBC SEC.4.24.1-4.24.7. |
| |
| GUEST LAUNDRY SHALL COMPLY W/FACBC SEC. |
| 9.1.1. |
| |
| WALLS AND FLOOR IN EMPLOYEE TOILET SHALL |
| BE NONABSORBENT TO A HEIGHT OF 4' PER |
| SBC SEC.1204.2. |
| |
| SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. |
| EQUIPMENT SHALL BE LISTED PER SGC SEC. |
| 402.1 |
| |
| SUBMIT COMPLETE GAS DRAWING FOR REVIEW. |
| SHOW TYPE OF PIPING,SIZES,BTU RATING OF |
| EACH APPLIANCE,ETC.COMPLY W/SGC CHAPTS. |
| 3-6 & NFPA 54,58.INCLUDE CALCULATIONS |
| FOR COMBUSTION AIR. |
| |
| MAX.TEMP.TO PUBLIC RESTROOMS SHALL NOT |
| EXCEED 110 DEG.PER FLA.ENERGY CODE SEC. |
| 412.1.ABCD.2.3.2. |
| |
| SHT.P-1.1.-REMOVE VACUUM BREAKERS FROM |
| WASHING MACHINE. |
| |
| SEE PLUMBING PLAN REVIEW STEP #2 FOR |
| CONTINUATION OF PLUMBING COMMENTS. |