Plan Review Notes
Plan Review Notes For Permit 00030112
Permit Number 00030112
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED*********************
  
 1)PROVIDE INFORMATION ON EXHAUST DUCT
 RISER MATERIAL
 2)KITCHEN HOOD AND EXHAUST DUCT WILL RE-
 QUIRE SEPARATE PERMIT AND MORE DETAILED
 PLANS
 3)PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4)PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 5)1997 SMC 304.8.6.1 REQUIRES SECONDARY
 DRAIN LINE TO BE RUN SEPARATELY FROM
 PRIMARY CONDENSATE DRAIN LINE
 6)PROVIDE DETAIL FOR PROTECTION OF DRYER
 VENT IN RATED WALL
 7)1997 SMC 610.6 REQUIRES SPECIFIC LOCA-
 TION AND INSTALLATION DETAILS FOR EACH
 FIRE DAMPER, FIRE DOOR, ETC. TO BE SHOWN
 AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER. THE FOLLOWING
 LOCATIONS DO NOT INDICATE FIRE DAMPERS
 M2.1 2-18X12 THRU RATED WALLS 2 PLACES
 2-14X12 THRU RATED MEETING ROOM
 WALLS
 2-12X8 THRU MEN'S AND WOMEN'S ROOM
 RATED WALLS
 NO FIRE DAMPERS AT COMBUSTION AIR
 OPENING
 2-18X10 IN RATED MAINTANANCE ROOM
 WALL
 PROVIDE DETAIL FOR FIRE PROTECTION OF
 OPENING @ 14" FLUE PIPE PENETRATING
 RATED WALL BY WATER HEATER ROOM
 M2-2 FIVE DUCTS LEAVING MECH ROOM 217
 ON 2ND FLOOR PLAN NO FIRE DAMPERS SHOWN
 M2-3 10X8 R/A DUCT @ STORAGE ROOM 318A
 RATED WALL
 10X8 R/A DUCT @ RM 320 RATED WALL
 M2-4 12X8 R/A DUCT @ RM 418 AND RM 420
  
 SEPARATE PERMITS AND PLANS WILL BE
 REQUIRED FOR WALK IN COOLERS/FREEZERS,
 KITCHEN HOOD, FIRE SUPPRESSION SYSTEM