Date |
Text |
2001-01-08 00:00:00 | *************DENIED********************* |
| |
| 1)PROVIDE INFORMATION ON EXHAUST DUCT |
| RISER MATERIAL |
| 2)KITCHEN HOOD AND EXHAUST DUCT WILL RE- |
| QUIRE SEPARATE PERMIT AND MORE DETAILED |
| PLANS |
| 3)PROVIDE OUTSIDE AIR CALCULATIONS PER |
| ASHRAE 62-89 |
| 4)PROVIDE AIR BALANCE SCHEDULE PER 1997 |
| SMC 501.2 |
| 5)1997 SMC 304.8.6.1 REQUIRES SECONDARY |
| DRAIN LINE TO BE RUN SEPARATELY FROM |
| PRIMARY CONDENSATE DRAIN LINE |
| 6)PROVIDE DETAIL FOR PROTECTION OF DRYER |
| VENT IN RATED WALL |
| 7)1997 SMC 610.6 REQUIRES SPECIFIC LOCA- |
| TION AND INSTALLATION DETAILS FOR EACH |
| FIRE DAMPER, FIRE DOOR, ETC. TO BE SHOWN |
| AND PROPERLY IDENTIFIED ON THE BUILDING |
| PLANS BY THE DESIGNER. THE FOLLOWING |
| LOCATIONS DO NOT INDICATE FIRE DAMPERS |
| M2.1 2-18X12 THRU RATED WALLS 2 PLACES |
| 2-14X12 THRU RATED MEETING ROOM |
| WALLS |
| 2-12X8 THRU MEN'S AND WOMEN'S ROOM |
| RATED WALLS |
| NO FIRE DAMPERS AT COMBUSTION AIR |
| OPENING |
| 2-18X10 IN RATED MAINTANANCE ROOM |
| WALL |
| PROVIDE DETAIL FOR FIRE PROTECTION OF |
| OPENING @ 14" FLUE PIPE PENETRATING |
| RATED WALL BY WATER HEATER ROOM |
| M2-2 FIVE DUCTS LEAVING MECH ROOM 217 |
| ON 2ND FLOOR PLAN NO FIRE DAMPERS SHOWN |
| M2-3 10X8 R/A DUCT @ STORAGE ROOM 318A |
| RATED WALL |
| 10X8 R/A DUCT @ RM 320 RATED WALL |
| M2-4 12X8 R/A DUCT @ RM 418 AND RM 420 |
| |
| SEPARATE PERMITS AND PLANS WILL BE |
| REQUIRED FOR WALK IN COOLERS/FREEZERS, |
| KITCHEN HOOD, FIRE SUPPRESSION SYSTEM |