Plan Review Notes For Permit 00030112 |
Permit Number |
00030112 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1-PAGES E1.2,E1.3,E1.4 ALL SHOW PANELS | | MOUNTED IN THE LINEN STORAGE ROOM SEE | | SECTIONS 240-24D, AND 384-7 WHY THEY | | CAN NOT BE LOCATED THERE! | | | | 2-PAGE E4.2 SHOWS A PANEL LABLED "PE" | | HOW IS THIS FED AND IT SHOWS NO LOADS | | OTHER THAN LIGHTING.ALSO THIS IS IN | | A SEPARATE STRUCTURE PLEASE TREAT AS | | PER CODE. | | | | 3-NO LOAD FOR "PE" SHOWN IN LOAD | | CALCULATION PLEASE CHECK | | | | 4-FAULT CURRENT RATING NEEDED FOR ALL | | SERVICE AND DISTRIBUTION EQUIPMENT!!! | | 110-9,10 |
|