2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE PROVIDE THE AIC RATING
 OF THE MAIN. THE MAIN MUST BE RATED FOR
 THE AVIALABLE FAULT CURRENT PER 110-9.
 PLEASE HAVE THIS LISTED ON THE RISER
 DIAGRAM. 215-5
  
 PLEASE SUBMIT THE ABOVEINFORMATION FOR
 REVIEW BEFORE ANY ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372