Plan Review Notes For Permit 00030083 |
Permit Number |
00030083 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** PROVISO *************** | | | | 1)NOTE: PLEASE PROVIDE THE AIC RATING | | OF THE MAIN. THE MAIN MUST BE RATED FOR | | THE AVIALABLE FAULT CURRENT PER 110-9. | | PLEASE HAVE THIS LISTED ON THE RISER | | DIAGRAM. 215-5 | | | | PLEASE SUBMIT THE ABOVEINFORMATION FOR | | REVIEW BEFORE ANY ROUGH INSPECTION IS | | CALLED IN. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|