Plan Review Notes For Permit 00021260 |
Permit Number |
00021260 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SIZE OF ACCESSIBLE STALLS SHALL COMPLY | | W/FACBC 4.1.6(B),4.17.3(SEE EXCEPTION & | | EXCEPTION:NEW CONSTRUCTION.) | | | | MIN.CLEAR FLOOR SPACE UNDER H.C..LAV. | | SHALL BE 29" PER FACBC SEC.4.19.2 AND | | TOP SHALL BE 34" MAX. | | | | HT.OF WATER CLOSET SHALL BE 19"PER FACBC | | SEC.4.16.3. | | | | SIZE ALL WASTE STACKS.COMPLY W/SPC SEC. | | 714.2. | | | | DRINKING FOUNTAIN NOT VENTED.COMPLY W/ | | SPC SEC.901.2. | | | | SUBMIT DETAIL OF H.C. DRINKING.COMPLY W/ | | FACBC SEC.4.15.2.,4.15.5 | | | | SHOW CLEAR FLOOR SPACE FOR URINAL.COMPLY | | W/FACBC SEC.4.18.3. | | | | ALL PIPING UNDER FIXTURES SHALL BE | | CONFIGURED TO PROTECT AGAINST IMPACT PER | | FACBC SEC.4.19.4. |
|