Plan Review Notes
Plan Review Notes For Permit 00021260
Permit Number 00021260
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SIZE OF ACCESSIBLE STALLS SHALL COMPLY
 W/FACBC 4.1.6(B),4.17.3(SEE EXCEPTION &
 EXCEPTION:NEW CONSTRUCTION.)
  
 MIN.CLEAR FLOOR SPACE UNDER H.C..LAV.
 SHALL BE 29" PER FACBC SEC.4.19.2 AND
 TOP SHALL BE 34" MAX.
  
 HT.OF WATER CLOSET SHALL BE 19"PER FACBC
 SEC.4.16.3.
  
 SIZE ALL WASTE STACKS.COMPLY W/SPC SEC.
 714.2.
  
 DRINKING FOUNTAIN NOT VENTED.COMPLY W/
 SPC SEC.901.2.
  
 SUBMIT DETAIL OF H.C. DRINKING.COMPLY W/
 FACBC SEC.4.15.2.,4.15.5
  
 SHOW CLEAR FLOOR SPACE FOR URINAL.COMPLY
 W/FACBC SEC.4.18.3.
  
 ALL PIPING UNDER FIXTURES SHALL BE
 CONFIGURED TO PROTECT AGAINST IMPACT PER
 FACBC SEC.4.19.4.