2001-01-08 00:00:00INDICATE TYPE OF PIPE BEING INSTALLED.
 COMPLY W.SGC SEC.306.
  
 SHOW DIMENSIONS OF ALL CUT LENGTHS OF
 PIPE TO ENSURE COMPLIANCE W/SGC TABLES
 305.4(A),305.4(F).
  
 IF CSST WILL BE USED INDICATE MANUF.OF
 CSST,THE PROPER EHD OF THE TUBING AND
 SUBMIT SIZING TABLE FROM THE MANUF.TO
 ENSURE PROPER SIZING.