Plan Review Notes For Permit 00021248 |
Permit Number |
00021248 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | INDICATE TYPE OF PIPE BEING INSTALLED. | | COMPLY W.SGC SEC.306. | | | | SHOW DIMENSIONS OF ALL CUT LENGTHS OF | | PIPE TO ENSURE COMPLIANCE W/SGC TABLES | | 305.4(A),305.4(F). | | | | IF CSST WILL BE USED INDICATE MANUF.OF | | CSST,THE PROPER EHD OF THE TUBING AND | | SUBMIT SIZING TABLE FROM THE MANUF.TO | | ENSURE PROPER SIZING. |
|