Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** PROVISO *************** | | | | 1)NOTE: NEED TO SHOW THE SIZE OF THE | | EXISTING SERVICE. NEED TO SUBMIT NEW | | LOAD CALCULATION TO INCLUDE NEW A/C | | LOAD BEINGADDED. | | | | 2)NOTE: AS REQ`D BY 210-52D/210-11-C-3 | | BATH CIRCUT TO BE DEDICATED. | | | | 3)NOTE: AS PER 110-16 NOTE CLEARENCE FOR | | AHU. | | | | 4)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1 | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | OUTSIDEALL SLEEPING ROOMS. | | | | PLEASE SUBMIT FOR REVIEW AND APPROVAL | | BEFORE ROUGH INSPECTION. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 X | | 8372 |
|