2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: LOAD CALCULATION STILL NEEDS TO
 BE RE-DONE. MCC-S IS STILL SHOWING LOAD
 FROM BEFORE WHEN DIMMER PACK LOADS
 WERE NOT FIGURED AT 125%. THIS WILL
 CHANGE LOAD CALCUALTION SHOWN ON MCC-S
  
 2)NOTE: PLEASE CAHNGE ON RISER.STILL
 SHOWS 293A
  
 3)NOTE: PLEASE CORRECT LOAD CALCULATION
 FOR MCC-S. CONNECTED LOAD SHOWN AT 175??
 WHEN CONNECTED LOAD FOR MOTORS ARE 189A
 WHICH IS WHAT YOU SHOW FURTHER DOWN.
 125% IS FIGURED FOR LARGEST MOTOR ONLY??
 WHERE IS THE 58AMPS COMING FROM.
  
 4)NOTE: PLEASE INCLUDE A NOTEON PLANS
 FOR CLASS A PROTECTION FOR PUMPS IN
 FOUNTAIN. PLEASE NOTE FOR SETTING OF
 GFI PROTECTION ON VFD`S LIKE YOU HAVE
 FOR LIGHTING.
  
 5)NOTE: PLEASE MAKE THE CORRECTION FOR
 THE AIC RATING OF MAIN ON SWITCHBOARD--
 "PB". I HAVE SPOKEN TO ELECTRICAL
 CONTRACTOR AND IT IS MY UNDERSTANDING
 THAT THE MAIN IS GOING TO BE INCREASED
 FOR THE AVAILABLE FAULT CURRENT??
 PLEASE VERIFY AND SHOW THE RATING OF
 MAIN BEING INSTALLED.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. WE ARE STILL WAITING FOR
 SHOP DRAWINGS/SPEC BOOKS??? PLEASE
 SUBMIT WITH PLANS. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 561-659-8096 EXT -
 8372