2001-01-08 00:00:00 | **************** UNSAT ***************** |
| |
| 1)NOTE: LOAD CALCULATION STILL NEEDS TO |
| BE RE-DONE. MCC-S IS STILL SHOWING LOAD |
| FROM BEFORE WHEN DIMMER PACK LOADS |
| WERE NOT FIGURED AT 125%. THIS WILL |
| CHANGE LOAD CALCUALTION SHOWN ON MCC-S |
| |
| 2)NOTE: PLEASE CAHNGE ON RISER.STILL |
| SHOWS 293A |
| |
| 3)NOTE: PLEASE CORRECT LOAD CALCULATION |
| FOR MCC-S. CONNECTED LOAD SHOWN AT 175?? |
| WHEN CONNECTED LOAD FOR MOTORS ARE 189A |
| WHICH IS WHAT YOU SHOW FURTHER DOWN. |
| 125% IS FIGURED FOR LARGEST MOTOR ONLY?? |
| WHERE IS THE 58AMPS COMING FROM. |
| |
| 4)NOTE: PLEASE INCLUDE A NOTEON PLANS |
| FOR CLASS A PROTECTION FOR PUMPS IN |
| FOUNTAIN. PLEASE NOTE FOR SETTING OF |
| GFI PROTECTION ON VFD`S LIKE YOU HAVE |
| FOR LIGHTING. |
| |
| 5)NOTE: PLEASE MAKE THE CORRECTION FOR |
| THE AIC RATING OF MAIN ON SWITCHBOARD-- |
| "PB". I HAVE SPOKEN TO ELECTRICAL |
| CONTRACTOR AND IT IS MY UNDERSTANDING |
| THAT THE MAIN IS GOING TO BE INCREASED |
| FOR THE AVAILABLE FAULT CURRENT?? |
| PLEASE VERIFY AND SHOW THE RATING OF |
| MAIN BEING INSTALLED.215-5 |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. WE ARE STILL WAITING FOR |
| SHOP DRAWINGS/SPEC BOOKS??? PLEASE |
| SUBMIT WITH PLANS. IF THERE ARE ANY |
| QUESTIONS PLEASE CALL 561-659-8096 EXT - |
| 8372 |