2001-01-08 00:00:00 | **************** UNSAT ***************** |
| |
| PLEASE NOTE THAT SOME OF THE ORIGINAL |
| COMMENTS WERENOT ADDRESSED. |
| |
| 1)NOTE: STILL NEED TO SEE W-5.7 FOR THE |
| LOAD THAT YOUARE SHOWING FOR LIGHTING. |
| YOU ARE SHOWWING LOAD FOR DIMMER PACK 'B |
| AT 234 AMPS. THIS IS CORRECT BUT ON W5.4 |
| YOU SHOW LOAD AT 200 AMPS??? |
| PLEASE CORRECT. |
| |
| 2)NOTE:ALSO, THE FEEDER WIRES FOR BOTH |
| DIMMER PACKS SHOWN ARE NOT RATED FOR THE |
| LOADS. |
| PLEASE CHANGE DTO CORRECT WIRE SIZE AS |
| PER 310-16.. |
| |
| 3)NOTE : SINCE THE LOAD SHOWN ON W5.4 |
| FOR DIMMER 'B' DOES NOT MATCH CORRECT |
| LOAD SHOWN ON W5.7. THE TOTAL LOAD FOR |
| MCC-S WILL HAVE TO CHANGE ALSO. |
| |
| 4)NOTE: AS PREVIOUS NOTES STATES, PLEASE |
| SHOW THE LOAD FOR MCC-S WITH THE ADDED |
| 25% FOR LARGEST MOTOR.PLEASE SHOW FIGS. |
| |
| 5)NOTE: YOU ARE SHOWING THE AIC RATING |
| FOR THE PANEL SWITCHBOARD 'PB' AS BEING |
| 10,000 AIC. PLEASE SUBMIT FAULT CURRENT |
| CALCULATIONS FOR THIS. YOU SHOW A 300KVA |
| TRANSFORMER NEXT TO PNAEL 'PB'. 110-9 |
| 215-5 |
| |
| **************************************** |
| |
| 1)NOTE: AFTER REVIEWING SPECS FOR THE |
| INSTALLATION OF THE "BENDER" GFI MODULES |
| ANY MODULES INSTALLED MUST MEET THE |
| UL 943 CLASS'A' WITH PROTECTION SET AT |
| 6MA OR LESS FOR PERSONNEL PROTECTION. |
| AS PER 680-51. |
| |
| 2)NOTE: ON W4.5 ALL FITTINGS USED FOR |
| GROUNDING/BONDING IN AND ABOUT FOUNTAIN |
| ARE TO BE LISTED FOR USE AS DIRECT |
| BURIAL AND CONCRETE ENCASEMENT. |
| |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL 561-659-8096 EXT 8372 |