2001-01-08 00:00:00**************** UNSAT *****************
  
 PLEASE NOTE THAT SOME OF THE ORIGINAL
 COMMENTS WERENOT ADDRESSED.
  
 1)NOTE: STILL NEED TO SEE W-5.7 FOR THE
 LOAD THAT YOUARE SHOWING FOR LIGHTING.
 YOU ARE SHOWWING LOAD FOR DIMMER PACK 'B
 AT 234 AMPS. THIS IS CORRECT BUT ON W5.4
 YOU SHOW LOAD AT 200 AMPS???
 PLEASE CORRECT.
  
 2)NOTE:ALSO, THE FEEDER WIRES FOR BOTH
 DIMMER PACKS SHOWN ARE NOT RATED FOR THE
 LOADS.
 PLEASE CHANGE DTO CORRECT WIRE SIZE AS
 PER 310-16..
  
 3)NOTE : SINCE THE LOAD SHOWN ON W5.4
 FOR DIMMER 'B' DOES NOT MATCH CORRECT
 LOAD SHOWN ON W5.7. THE TOTAL LOAD FOR
 MCC-S WILL HAVE TO CHANGE ALSO.
  
 4)NOTE: AS PREVIOUS NOTES STATES, PLEASE
 SHOW THE LOAD FOR MCC-S WITH THE ADDED
 25% FOR LARGEST MOTOR.PLEASE SHOW FIGS.
  
 5)NOTE: YOU ARE SHOWING THE AIC RATING
 FOR THE PANEL SWITCHBOARD 'PB' AS BEING
 10,000 AIC. PLEASE SUBMIT FAULT CURRENT
 CALCULATIONS FOR THIS. YOU SHOW A 300KVA
 TRANSFORMER NEXT TO PNAEL 'PB'. 110-9
 215-5
  
 ****************************************
  
 1)NOTE: AFTER REVIEWING SPECS FOR THE
 INSTALLATION OF THE "BENDER" GFI MODULES
 ANY MODULES INSTALLED MUST MEET THE
 UL 943 CLASS'A' WITH PROTECTION SET AT
 6MA OR LESS FOR PERSONNEL PROTECTION.
 AS PER 680-51.
  
 2)NOTE: ON W4.5 ALL FITTINGS USED FOR
 GROUNDING/BONDING IN AND ABOUT FOUNTAIN
 ARE TO BE LISTED FOR USE AS DIRECT
 BURIAL AND CONCRETE ENCASEMENT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372