Plan Review Notes
Plan Review Notes For Permit 00020939
Permit Number 00020939
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: MOTOR LOAD ON MCC-S;NEEDS TO
 SHOW 25% OF LARGEST MOTOR SHOWN IN TOTAL
 LOAD.THAT WILL AFFECT TOTAL LOAD SHOWN.
  
 2)NOTE: YOU SHOW ON W5-6 AND W5-7
 LOAD FOR LIGHTING AT 125%. THIS IS
 CORRECT BUT ON W5-4 YOU DO NOT SHOW THE
 SAME LOAD CARRIED OVER FROM THOSE PAGES.
  
 3)NOTE: FEEDERS FOR DIMMER PACKS NEED TO
 BE RATED FOR THE LOADS. ALSO CHECK TO
 MAKE SURE THAT OVERCURRENT PROTECTION
 IS ADEQUATE. FEEDERS MUST BE SIZED
 ACCORDINGLY.
  
 4)NOTE: SINCE THE LOADS FOR THE DIMMER
 PACKSARE HIGHER THEN NEW TOTAL LOAD
 WILL CHANGE TRANSFORMER T-1 LOAD.
  
 PLEASE SUBMIT NEW REVISED PLANS FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372