Plan Review Notes For Permit 00020939 |
Permit Number |
00020939 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: MOTOR LOAD ON MCC-S;NEEDS TO | | SHOW 25% OF LARGEST MOTOR SHOWN IN TOTAL | | LOAD.THAT WILL AFFECT TOTAL LOAD SHOWN. | | | | 2)NOTE: YOU SHOW ON W5-6 AND W5-7 | | LOAD FOR LIGHTING AT 125%. THIS IS | | CORRECT BUT ON W5-4 YOU DO NOT SHOW THE | | SAME LOAD CARRIED OVER FROM THOSE PAGES. | | | | 3)NOTE: FEEDERS FOR DIMMER PACKS NEED TO | | BE RATED FOR THE LOADS. ALSO CHECK TO | | MAKE SURE THAT OVERCURRENT PROTECTION | | IS ADEQUATE. FEEDERS MUST BE SIZED | | ACCORDINGLY. | | | | 4)NOTE: SINCE THE LOADS FOR THE DIMMER | | PACKSARE HIGHER THEN NEW TOTAL LOAD | | WILL CHANGE TRANSFORMER T-1 LOAD. | | | | PLEASE SUBMIT NEW REVISED PLANS FOR | | REVIEW AND APPROVAL. IF THERE ARE ANY | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|