2001-01-08 00:00:001)SUBMIT COPY OF GAS TABLE UTILIZED IN
 DESIGN OF THE PIPING SYSTEM.COMPLY W/
 STANDARD GAS CODE SECS.1003.4.1,
 1003.4.2,1003.4.3
  
 2)SHT.P-1-UTILITIES DEMAND LEGEND NOTES
 250' RUN AND KITCHEN EQUIPMENT SCH.NOTES
 100'RUN FOR GAS PIPE.CLARIFY AND COMPLY
 W/SGC.
  
 3)SHT.P-4-GAS PIPING CANNOT PENETRATE
 STAIRWAY ENCLOSURE PER SBC SEC.1006.1.3,
 1006.1.3.1(SEE GAS REGULATOR ALSO.)
  
 4)COMPLY W/ATTACHED GAS REQS.
  
 5)SHOW PRESSURE DROP OF SYSTEM ON THE
 PLANS.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE.
 PLUMBING PLANS EXAMINER.