2001-01-08 00:00:00PLANS SHALL BE REVIEWED AND APPROVED BY
 THE DEPT.OF BUSINESS AND PROFESSIONAL
 REGULATION PRIOR TO REVIEW BY THIS DEPT.
 PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET
 THERE IS NO "A-3"OCCUPANCY IN THE SBC.
 SBC 304.2.1.
  
 SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC SEC.407.1.3.
 PLANS NOTE OCCUPANT LOAD AS 416 PERSONS-
 AND DO NOT COMPLY W/SPC TABLE 407 OR FLA
 STATUTE 553.141.FOR MIN.FIXTURE REQS.
  
 PLANS SHALL BEAR THE CITY PLACE LANDLORD
 APPROVAL STAMP PRIOR TO APPROVAL FROM
 THIS DEPT.
  
 SHOW INSIDE CLEAR DIMENSIONS (LXW) OF
 ACCESSIBLE TOILET ROOMS AND STALLS.
 COMPLY W/FACBC SECS.4.16,4.17,FIGURES#28
 & #30.TOILETS TO BE 18"FROM WALL,NOT 19"
  
 SHT.P-1-(INSULATION TABLE FOR WATER
 PIPING )-INSULATION THICKNESS FOR PIPING
 SHALL COMPLY W/FLA.ENERGY CODE TABLE
 4-11.(FOR PIPING 1" AND LESS MIN.THICK-
 NESS SHALL BE 1")
  
 WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC 610.4.1(THERE ARE FIXTURES THAT
 CANNOT BE ISOLATED W/O SHUTTING DOWN
 ENTIRE SYSTEM.REVIEW WATER RISER AND
 COMPLY.SEE SERVICE STATION ,BAKERY,2ND
 FLR.TOILET ROOMS,ETC.)
  
 FIXTURE UNIT LOAD FOR SANITARY AND
 GREASY WASTE SYSTEM SHALL COMPLY W/SPC
 TABLES 713.1,713.2.REVISE FIXTURE UNIT
 LOAD.
  
 SUBMIT DETAILS FOR GAS VENT ON WATER
 HEATER.INDICATE TYPE OF VENT,HEIGHT,ETC.
 COMPLY W/SGC SECS.605.3,608.3.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR GAS APPLIANCES.COMPLY W/SGC SEC.
 402.4.4.
  
 INSTALLATION OF WATER HEATER SHALL
 COMPLY W/SGC SEC.405.1.1.SUBMIT MANUF.
 SHEETS FOR WATER HEATER AND ALL OTHER
 GAS EQUIPMENT.SGC SEC.402.1.
  
 ALL GAS VALVES SHALL BE READILY ACCESS-
 IBLE PER SGC 403.1.2.PLANS SHOW VALVES
 BEHIND EQUIPMENT.
  
 SHT.K-2.1-NO WATER ABOVE 140 DEGREES
 SHALL DISCHARGE INTO THE DRAINAGE SYSTEM
 PER SPC SEC.807.3.(SEE WATER HEATER NOTE
  
 SHT.P-8-CLARIFY BTU LOAD OF GAS WATER
 HEATER.PLANS NOTE 1800 & 1852 CFH.
  
 ELEVATOR SUMP DRAIN IS NOT SHOWN ON
 WASTE PIPING RISER.DISCHARGE SHALL BE TO
 SANITARY SYSTEM NOT GREASY WASTE.IF
 ELEVATOR IS HYDRAULIC,DRAIN SHALL FIRST
 PASS THRU AN OIL INTERCEPTOR PRIOR TO
 DISCHARGE TO SANITARY SYSTEM PER SPC
 SEC.1004.1,1004.5,1004.8.
  
 A UNION IS REQD.DOWNSTREAM OF ELECTRONIC
 GAS VALVE TO ALLOW FOR REMOVAL/REPLACE-
 MENT.NFPA 54 SEC.5.5.4.
  
 GAS SYSTEM IS UNDERSIZED FOR THE TOTAL
 BTU LOAD AND DISTANCE FROM POINT OF
 DELIVERY PER SGC TABLE 305.4(A).
  
 PLEASE CALL 561-659-8096 EXT.8377 IF YOU
 HAVE ANY QUESTIONS.T.LARGE.