2001-01-08 00:00:00 | PLANS SHALL BE REVIEWED AND APPROVED BY |
| THE DEPT.OF BUSINESS AND PROFESSIONAL |
| REGULATION PRIOR TO REVIEW BY THIS DEPT. |
| PER COUNTYWIDE AMENDMENTS TO SPC |
| SEC.101.4.7. |
| |
| CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET |
| THERE IS NO "A-3"OCCUPANCY IN THE SBC. |
| SBC 304.2.1. |
| |
| SUBMIT OCCUPANT LOAD BASED ON HABITABLE |
| FLOOR SPACE PER SPC SEC.407.1.3. |
| PLANS NOTE OCCUPANT LOAD AS 416 PERSONS- |
| AND DO NOT COMPLY W/SPC TABLE 407 OR FLA |
| STATUTE 553.141.FOR MIN.FIXTURE REQS. |
| |
| PLANS SHALL BEAR THE CITY PLACE LANDLORD |
| APPROVAL STAMP PRIOR TO APPROVAL FROM |
| THIS DEPT. |
| |
| SHOW INSIDE CLEAR DIMENSIONS (LXW) OF |
| ACCESSIBLE TOILET ROOMS AND STALLS. |
| COMPLY W/FACBC SECS.4.16,4.17,FIGURES#28 |
| & #30.TOILETS TO BE 18"FROM WALL,NOT 19" |
| |
| SHT.P-1-(INSULATION TABLE FOR WATER |
| PIPING )-INSULATION THICKNESS FOR PIPING |
| SHALL COMPLY W/FLA.ENERGY CODE TABLE |
| 4-11.(FOR PIPING 1" AND LESS MIN.THICK- |
| NESS SHALL BE 1") |
| |
| WATER SUPPLY CONTROL SHALL COMPLY W/ |
| SPC 610.4.1(THERE ARE FIXTURES THAT |
| CANNOT BE ISOLATED W/O SHUTTING DOWN |
| ENTIRE SYSTEM.REVIEW WATER RISER AND |
| COMPLY.SEE SERVICE STATION ,BAKERY,2ND |
| FLR.TOILET ROOMS,ETC.) |
| |
| FIXTURE UNIT LOAD FOR SANITARY AND |
| GREASY WASTE SYSTEM SHALL COMPLY W/SPC |
| TABLES 713.1,713.2.REVISE FIXTURE UNIT |
| LOAD. |
| |
| SUBMIT DETAILS FOR GAS VENT ON WATER |
| HEATER.INDICATE TYPE OF VENT,HEIGHT,ETC. |
| COMPLY W/SGC SECS.605.3,608.3. |
| |
| SUBMIT CALCULATIONS FOR COMBUSTION AIR |
| FOR GAS APPLIANCES.COMPLY W/SGC SEC. |
| 402.4.4. |
| |
| INSTALLATION OF WATER HEATER SHALL |
| COMPLY W/SGC SEC.405.1.1.SUBMIT MANUF. |
| SHEETS FOR WATER HEATER AND ALL OTHER |
| GAS EQUIPMENT.SGC SEC.402.1. |
| |
| ALL GAS VALVES SHALL BE READILY ACCESS- |
| IBLE PER SGC 403.1.2.PLANS SHOW VALVES |
| BEHIND EQUIPMENT. |
| |
| SHT.K-2.1-NO WATER ABOVE 140 DEGREES |
| SHALL DISCHARGE INTO THE DRAINAGE SYSTEM |
| PER SPC SEC.807.3.(SEE WATER HEATER NOTE |
| |
| SHT.P-8-CLARIFY BTU LOAD OF GAS WATER |
| HEATER.PLANS NOTE 1800 & 1852 CFH. |
| |
| ELEVATOR SUMP DRAIN IS NOT SHOWN ON |
| WASTE PIPING RISER.DISCHARGE SHALL BE TO |
| SANITARY SYSTEM NOT GREASY WASTE.IF |
| ELEVATOR IS HYDRAULIC,DRAIN SHALL FIRST |
| PASS THRU AN OIL INTERCEPTOR PRIOR TO |
| DISCHARGE TO SANITARY SYSTEM PER SPC |
| SEC.1004.1,1004.5,1004.8. |
| |
| A UNION IS REQD.DOWNSTREAM OF ELECTRONIC |
| GAS VALVE TO ALLOW FOR REMOVAL/REPLACE- |
| MENT.NFPA 54 SEC.5.5.4. |
| |
| GAS SYSTEM IS UNDERSIZED FOR THE TOTAL |
| BTU LOAD AND DISTANCE FROM POINT OF |
| DELIVERY PER SGC TABLE 305.4(A). |
| |
| PLEASE CALL 561-659-8096 EXT.8377 IF YOU |
| HAVE ANY QUESTIONS.T.LARGE. |