Date |
Text |
2001-01-08 00:00:00 | ******CONTINUATION OF PLUMBING COMMENTS | | SHT.P-8-CLARIFY CORRECT BTU LOAD OF | | WATER HEATER.(NOTED AS 1800 CFH AND ALSO | | 1852 CFH.) | | | | MAX.TEMPERATURE OF HOT WATER TO REST- | | ROOMS SHALL BE 110 DEGREES PER FLA. | | ENERGY CODE SEC.412.1ABCD.2.3.2(2). | | | | SHT.P-9-WATER RISER SHALL CLEARLY SHOW | | ENTIRE SCOPE OF WORK(WATER RISER DOES | | NOT REFLECT ENTIRE 2ND FLR.)COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1. | | | | THE MINIMUM PLUMBING FIXTURE REQS.SHALL | | COMPLY W/FLA.STATUTE 553.141.(3). | | | | PLANS SHALL BE SIGNED AND SEALED PER | | FLA.STATUTE 471 AND COUNTYWIDE AMENDMENT | | TO SPC SEC.104.2.3. | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | REACHED AT (561)659-8026,EXT.8377. |
|