2001-01-08 00:00:00******CONTINUATION OF PLUMBING COMMENTS
 SHT.P-8-CLARIFY CORRECT BTU LOAD OF
 WATER HEATER.(NOTED AS 1800 CFH AND ALSO
 1852 CFH.)
  
 MAX.TEMPERATURE OF HOT WATER TO REST-
 ROOMS SHALL BE 110 DEGREES PER FLA.
 ENERGY CODE SEC.412.1ABCD.2.3.2(2).
  
 SHT.P-9-WATER RISER SHALL CLEARLY SHOW
 ENTIRE SCOPE OF WORK(WATER RISER DOES
 NOT REFLECT ENTIRE 2ND FLR.)COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 THE MINIMUM PLUMBING FIXTURE REQS.SHALL
 COMPLY W/FLA.STATUTE 553.141.(3).
  
 PLANS SHALL BE SIGNED AND SEALED PER
 FLA.STATUTE 471 AND COUNTYWIDE AMENDMENT
 TO SPC SEC.104.2.3.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT (561)659-8026,EXT.8377.