Plan Review Notes
Plan Review Notes For Permit 00020850
Permit Number 00020850
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE REVIEWED AND APPROVED BY
 DEPT.OF BUSINESS AND PROFESSIONAL REG.
 PRIOR TO REVIEW BY THIS DEPT.PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 CLARIFY TYPE OF OCCUPANCY ON TITLE SHEET
 THERE IS NO "A-3" OCCUPANCY IN THE SBC.
 SBC 304.2.1.
  
 SUBMIT OCCUPANT LOAD BASED ON HABITABLE
 FLOOR SPACE PER SPC SEC.407.1.3.THE MIN.
 REQUIRED NUMBER AND TYPE OF PLUMBING
 FIXTURES SHALL COMPLY W/SPC. TABLE 407.
  
 CLEARLY SHOW THE REQD.WHEELCHAIR TURN-
 ING SPACE IN THE TOILET STALLS PER
 FACBC SEC.4.2.3.
  
 GREASE TRAP SHALL COMPLY W/CITY OF WPB
 UTILITIES REQS.CONTACT ROD COMPO AT(561)
 835-7423.
  
 CLEARLY SHOW SIZES OF ACCESSIBLE TOILET
 ROOMS AND HANDICAPSTALLS.COMPLY W/
 FACBC 4.16,4.17,FIGURE 28, FIG,30.(LXW)
  
 SHT.P-1(INSULATION TABLE FOR WTR.PIPING)
 INSULATION THICKNESS FOR PIPING SHALL
 COMPLY W/FLA.ENERGY CODE TABLE 4-11.
  
 SHT.P-2-DRAIN FROM BAKERY,BAR & SERVICE
 AREAS SHALL DRAIN TO THE GREASY WASTE
 SYSTEM,NOT THE SANITARY.SPC SEC.1004.1,
 1004.4.
  
 SUBMIT DETAIL OF DETERGENT PUMPS AND
 WATER CONNECTION THERETO.A BACKFLOW
 PREVENTION DEVICE SHALL BE INSTALLED ON
 THE WATER CONNECTION PER SPC SEC.606.1.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SECS.610.4.1,610.4.2.
  
 SHT.P-7-THE DISTANCE OF A WATER CLOSET
 TRAP FROM ITS VENT SHALL NOT EXCEED
 5 FT.PER COUNTYWIDE AMENDMENTS TO SPC
 TABLE 908.1,FOOTNOTE #2.
  
 SHT.P-7-FIXTURE BRANCHES AND WATER
 CLOSETS ARE NOT PERMITTED ON HORIZ.WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1,911.1.3.(SEE MEN'S AND
 WOMEN'S RESTROOM.)
  
 THE SANITARY RISER DOES NOT SHOW ALL
 PLUMBING FIXTURES.SUBMIT REVISED
 SANITARY RISER THAT CLEARLY REFLECTS
 ENTIRE SCOPE OF WORK TO BE PERFORMED.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
 (SEE WOMEN'S R.R., 3" SAN.TO 2ND.FLR.,
 2ND FLR. PLBG.,ETC.)
  
 FIXTURE UNIT LOAD SHALL COMPLY W/TABLE
 713.1,713.2.REVISE FIXTURE UNIT LOAD.
  
 WATER FILTRATION/TREATMENT SYSTEMS SHALL
 COMPLY W/SPC SEC.615.1,615.2.,NSF 42,53,
 58.SUBMIT MANUF.SHEETS.
  
 SUBMIT DETAILS ON GAS VENT FOR WATER
 HEATER.INDICATE TYPE OF VENT,HEIGHT
 ABOVE ROOF,ETC.COMPLY W/SGC SECS.605.3,
 608.3.
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR.
 COMPLY W/SGC SECS.402.4.4
  
 INSTALLATION OF WATER HEATER ON ROOF
 SHALL COMPLY W/SGC SEC.405.
  
  
  
  
  
 CLEARLY SHOW EMERGENCY SHUT-OFF VALVE/
 ELECTRONIC GAS VALVE ON GAS RISER.
 COMPLY W/NFPA 54 SEC.5.5.4.
  
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIPMENT SHALL BE APPROVED PER SGC
 402.1.
  
 ALL GAS VALVES SHALL BE ACCESSIBLE AND
 LOCATED PER SGC SEC.403.1.2.,INCLUDING
 ELECTRONIC GAS VALVE.(SEE SHT.K-3.1)
  
 SHT.K-2.1-NO WATER ABOVE 140 DEGREES
 SHALL DISCHARGE INTO THE DRAINAGE
 SYSTEM PER SPC SEC.807.3.