1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CORRECTED BY REVISION**************** | | | | 1) EQUIPMENT RACK TO HAVE MIN. 18" CLEAR | | ANCE BETWEEN ROOF SURFACE AND BOTTOM OF | | SUPPORT STRUCTURE OF STANDS (LOCAL CODE) | | 2) EXHAUST TERMINATION FOR GREASE HOODS | | TO BE MIN. 40" ABOVE ROOF SURFACE 1997 | | SMC 506.1 | | 3) SLOPE FOR GREASE DUCT TO BE MIN. 1" | | PER FOOT 1997 SMC 505.4 | | 4) OUTSIDE AIR INTAKE TO BE MIN. 10' | | FROM EXHAUST AIR OUTLET. PLAN SCALE SHOW | | LESS | | 5) NEED SPECS ON CHILLED WATER PIPING | | MATERIAL. NOTE COPPER TO BE JOINED BY | | BRAZING 1997 SMC TABLE 1205 | | 6) SEPARATE PERMITS REQUIRED FOR HOODS, | | SUPPRESSION SYSTEMS, AND COOLER/FREEZERS |
|