Plan Review Notes
Plan Review Notes For Permit 00020850
Permit Number 00020850
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE:PLEASE SHOW THE COMPLETE LOAD
 CALCULATION. TO INCLUDE THE SQ.FT AND
 CONTINUOUS LOADS. ALL PER ART;220
  
 2)NOTE:PLEASE SHOW COMPLETE GROUNDING
 SYSTEM ON SERVICE.YOU SHOW GROUND WIRES,
 BUT PLEASE SHOW WHERE THEY ARE GOING.
 PER 250 AND 215-5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372