2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: LOAD CALCULATION DOES NOT MEET
 ART 220 OF THE NEC . PLEASE CORRECT.
  
 2)NOTE: EQUIPMENT GROUNDING CONDUCTOR
 IS REQ`D FROM MAIN HOUSE IN CONDUIT WITH
 FEEDERS FOR PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BLDG. STEEL AS PER 250-50 AND
 ANY METAL COLD WATER PIPE AT DETACHED
 BLDG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372