Plan Review Notes For Permit 00020370 |
Permit Number |
00020370 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED | | ALL PROBLEMS IN GUEST QUARTERS; | | 1.FIRST FLOOR, CFM'S REQUIRED FOR ALL | | DROPS. | | 2.SECOND FLOOR, RETURN AIR NOT PERMITED | | IN BATHROOM. | | 3.A/C UNIT TO SMALL FOR CFM'S SHOWN. | | 790 CFM WITH ONE DROP MISSING | | CALCULATIONS. 1 1/2 TON A/H WILL | | PROVIDE ONLY 600 CFM. |
|