Plan Review Notes
Plan Review Notes For Permit 00020366
Permit Number 00020366
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00THE DESIGN COMPLIANCE FORM STATES
 THAT SBC 97 WAS USED ANDPLAN C1 SAYS
 RATIONAL ANALYSIS WAS USED.CLARIFY
  
 THE DESIGN COMPLIANCE FORM STATES A MEAN
 ROOF HT OF 15 FT.AND I CALCULATE THE
 MEAN HT TO BE 17 FT.
  
 THE ROOF TRUSSES LOADS STATED ON PLAN
 S-2.1 STATES A BASIC WIND PRESSURE OF
 25.5 PSF. AND THE DESIGN COMPLIANCE FORM
 STATES 24.7 PSF.THE PRESSURES ARE FROM
 TWO DIFFERENT SOURCES?CLARIFY
  
 PROVIDE THE CALCULATIONS FOR ATTACHING
 THE ROOF TILES AS PER THE PRODUCT APPROV
 SEE TABLE 2.
  
 THE DESIGN COMPLIANCE FORM AND PLANS
 ARE REQUIRED TO STATE THE EXACT ADDRESS
 OF THE STRUCTURE
  
 NEEDS ENERGY CALCULATIONS FORM 600