Plan Review Notes For Permit 00020363 |
Permit Number |
00020363 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED | | | | 1)DESIGN COMPLIANCE FORM SPECIFIES A | | MEAN ROOF HEIGHT TO BE 15',I CALCULATE | | IT TO BE 24'10" CLARIFY & RECALCULATE | | ALL UPLIFTS,PROVIDE CORRECTED FORM. | | 2)EXTERIOR DOOR AT GUEST SUITE DOES NOT | | COMPLY WITH EGRESS REQUIREMENTS.EGRESS | | DOORS SHALL BE OF THE SIDE SWINGING | | TYPE AND SHALL PROVIDE A CLEAR OPENING | | OF NOT LESS THAN 32". 97SBC-1012.1 | | 3)PROVIDE ENERGY CALCS.AND MANUAL J FOR | | MAIN HOUSE | | 4)PLANS INDICATE 50GAL WATER HEATER FORM | | 600A-97 & EPL DISPLAY CARD INDICATE | | 30 GAL. WATER HEATER,CLARIFY | | 5)PROVIDE PRODUCT APPROVALS FOR INSWING | | EXTERIOR DOOR AT GUEST SUITE | | 6)PROVIDE PRODUCT APPROVALS FOR STORM | | PANELS | | 7)PROVIDE SOIL BEARING TEST REPORT PRIOR | | TO FIRST INSPECTION |
|