2001-01-08 00:00:00 | DESIGN COMPLIANCE FORM SPECIFYS SBC 1997 |
| THE NOTES ON PLAN S-2.1 SPECIFYS ASCE 7- |
| 93. CLARIFY WHICH DESIGN CRITERIA WAS |
| USED.NOTE THAT ASCE 7-93 IS INVALID |
| EDITION & ASCE 7-95 IS THE VALID CRITERI |
| ALSO NOTE THAT ASCE 7-95 CLASSIFYS OUR |
| LOCATION IN A 145 MPH ZONE. |
| |
| THERE ARE NOTES ON THE PLAN THAT SPECIFY |
| THAT RATIONAL ANALYSIS WAS USED IN THE |
| DESIGN. CLARIFY HOW THE WIND PRESSURES |
| WERE DETERMINED USING THIS METHOD. |
| |
| |
| DESIGN PARAMETERS SPECIFYS REQUIRING |
| A 2500 PSF SOIL BEARING PRESSURE AND ON |
| PLAN S1 THE SOIL PRESSURE STATEMENT |
| SPECIFYS A 2000 PSF. CLARIFY |
| |
| |
| THE DESIGN COMPLIANCE FORM SPECIFYS A |
| MEAN ROOF HEIGHT OF 15 FEET. I CALCULATE |
| THE MEAN ROOF HT TO BE 16.6.CLARIFY |
| |
| |
| PLAN S-2.1, ROOF TRUSS SUPERLOADS BOX |
| SPECIFYS A BASIC WIND PRESSURE OF 26.3. |
| THIS PRESSURE DOES NOT COINCIDE WITH THE |
| PRESSURES IN TABLE 1606.2A SBC FOR A |
| MEAN ROOF HT OF 15 FEET. |
| |
| PROVIDE THE CALCULATIONS FOR ATTACHING |
| THE ROOF TILES AS PER THE PRODUCT APPROV |
| SEE TABLE 2 |
| |
| NEEDS ENERGY CALCULATIONS FORM 600 |