Plan Review Notes
Plan Review Notes For Permit 00020362
Permit Number 00020362
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DESIGN COMPLIANCE FORM SPECIFYS SBC 1997
 THE NOTES ON PLAN S-2.1 SPECIFYS ASCE 7-
 93. CLARIFY WHICH DESIGN CRITERIA WAS
 USED.NOTE THAT ASCE 7-93 IS INVALID
 EDITION & ASCE 7-95 IS THE VALID CRITERI
 ALSO NOTE THAT ASCE 7-95 CLASSIFYS OUR
 LOCATION IN A 145 MPH ZONE.
  
 THERE ARE NOTES ON THE PLAN THAT SPECIFY
 THAT RATIONAL ANALYSIS WAS USED IN THE
 DESIGN. CLARIFY HOW THE WIND PRESSURES
 WERE DETERMINED USING THIS METHOD.
  
  
 DESIGN PARAMETERS SPECIFYS REQUIRING
 A 2500 PSF SOIL BEARING PRESSURE AND ON
 PLAN S1 THE SOIL PRESSURE STATEMENT
 SPECIFYS A 2000 PSF. CLARIFY
  
  
 THE DESIGN COMPLIANCE FORM SPECIFYS A
 MEAN ROOF HEIGHT OF 15 FEET. I CALCULATE
 THE MEAN ROOF HT TO BE 16.6.CLARIFY
  
  
 PLAN S-2.1, ROOF TRUSS SUPERLOADS BOX
 SPECIFYS A BASIC WIND PRESSURE OF 26.3.
 THIS PRESSURE DOES NOT COINCIDE WITH THE
 PRESSURES IN TABLE 1606.2A SBC FOR A
 MEAN ROOF HT OF 15 FEET.
  
 PROVIDE THE CALCULATIONS FOR ATTACHING
 THE ROOF TILES AS PER THE PRODUCT APPROV
 SEE TABLE 2
  
 NEEDS ENERGY CALCULATIONS FORM 600