Plan Review Notes
Plan Review Notes For Permit 00020361
Permit Number 00020361
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DESIGN COMPLIANCE FORM SPECIFYS SBC 1997
 THE NOTES ON PLAN S-2.1 SPECIFYS ASCE 7/
 93.CLARIFY WHICH DESIGN CRITERIA WAS
 USED.NOTE THAT ASCE 7/93 IS INVALID
 EDITION & ASCE 7/95 IS THE VALID CRITERI
 ALSO NOTE THAT ASCE 7/95 CLASSIFYS OUR
 LOCATION AS A 145 MPH ZONE. PLAN C1 SPEC
 SBC FOR WIND, S2-1 SPECIFYS ASCE 7-95 ?
  
 THERE ARE NOTES ON THE PLAN THAT SPECIFY
 THAT RATIONAL ANALYSIS WAS USED IN THE
 DESIGN.CLARIFY HOW THE WIND PRESSURES
 WERE DETERMINED USING THIS METHOD OR HOW
 IS THIS USED FOR THE DESIGN CALCULATIONS
  
 DESIGN PARAMETERS SPECIFYS REQUIRING A
 2500 PSF SOIL BEARING PRESSURE AND ON
 PLAN S1 2000 PSF IS SPECIFIED.CLARIFY
  
  
 THE DESIGN COMPLIANCE FORM SPECIFYS A
 MEAN ROOF HEIGHT OF 15 FEET.I CALCULAT
 THE MEAN HT TO BE 16.5 FT. CLARIFY AND
 RECALCULATE ALL UPLIFTS.
  
  
 PLAN S-2.1 , ROOF TRUSS SUPERLOADS BOX
 SPECIFYS A BASIC WIND PRESSURE OF 26.3.
 THIS PRESSURE DOES NOT COINCIDE WITH THE
 PRESSURES IN TABLE 1606.2A SBC FOR A
 MEAN ROOF HEIGHT OF 15 FEET. THIS MAY
 BE FROM ASCE 7, BUT THE DESIGN COMPLIANC
 FORM SPECIFYS SBC.CLARIFY
  
 PROVIDE THE CALCULATIONS FOR ATTACHING
 THE ROOF TILES AS PER THE PRODUCT
 APPROVAL, SEE TABLE 2
  
 THE DESIGN COMPLIANCE FORM AND THE PLANS
 ARE REQUIRED TO HAVE THE EXACT ADDRESS
 ON BOTH.
  
 PROVIDE ENERGY CALCULATION FORM 600