2001-01-08 00:00:00 | DESIGN COMPLIANCE FORM SPECIFYS SBC 1997 |
| THE NOTES ON PLAN S-2.1 SPECIFYS ASCE 7/ |
| 93.CLARIFY WHICH DESIGN CRITERIA WAS |
| USED.NOTE THAT ASCE 7/93 IS INVALID |
| EDITION & ASCE 7/95 IS THE VALID CRITERI |
| ALSO NOTE THAT ASCE 7/95 CLASSIFYS OUR |
| LOCATION AS A 145 MPH ZONE. PLAN C1 SPEC |
| SBC FOR WIND, S2-1 SPECIFYS ASCE 7-95 ? |
| |
| THERE ARE NOTES ON THE PLAN THAT SPECIFY |
| THAT RATIONAL ANALYSIS WAS USED IN THE |
| DESIGN.CLARIFY HOW THE WIND PRESSURES |
| WERE DETERMINED USING THIS METHOD OR HOW |
| IS THIS USED FOR THE DESIGN CALCULATIONS |
| |
| DESIGN PARAMETERS SPECIFYS REQUIRING A |
| 2500 PSF SOIL BEARING PRESSURE AND ON |
| PLAN S1 2000 PSF IS SPECIFIED.CLARIFY |
| |
| |
| THE DESIGN COMPLIANCE FORM SPECIFYS A |
| MEAN ROOF HEIGHT OF 15 FEET.I CALCULAT |
| THE MEAN HT TO BE 16.5 FT. CLARIFY AND |
| RECALCULATE ALL UPLIFTS. |
| |
| |
| PLAN S-2.1 , ROOF TRUSS SUPERLOADS BOX |
| SPECIFYS A BASIC WIND PRESSURE OF 26.3. |
| THIS PRESSURE DOES NOT COINCIDE WITH THE |
| PRESSURES IN TABLE 1606.2A SBC FOR A |
| MEAN ROOF HEIGHT OF 15 FEET. THIS MAY |
| BE FROM ASCE 7, BUT THE DESIGN COMPLIANC |
| FORM SPECIFYS SBC.CLARIFY |
| |
| PROVIDE THE CALCULATIONS FOR ATTACHING |
| THE ROOF TILES AS PER THE PRODUCT |
| APPROVAL, SEE TABLE 2 |
| |
| THE DESIGN COMPLIANCE FORM AND THE PLANS |
| ARE REQUIRED TO HAVE THE EXACT ADDRESS |
| ON BOTH. |
| |
| PROVIDE ENERGY CALCULATION FORM 600 |