Plan Review Notes For Permit 00020078 |
Permit Number |
00020078 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | | | | | *****************PROVISO**************** | | | | SBC 104.2.2 | | | | 1)PROVIDE SOIL REPORT | | | | 2)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVALS FOR ALL EXTERIOR DOORS | | | | 3)PROVIDE MINIMUM OF 12" FOOTING DEPTH | | BELOW FINISH GRADE. 1997 SBC 1804.1.3 | | | | 4)PROVIDE MINIMUM OF 4" FROM FINISH | | GRADE TO TOP OF FINISH FLOOR | | 1997 CITY AMENDMENTS 1804.1.9 | | | | 5)PROVIDE 2 CURRENT COPIES OF PRODUCT | | APPROVALS FOR STORM PANELS WITH KEY PLAN | | AND INSTALLATION SCHEDULE WITH SPECIFIC | | ANCHORS TO BE USED. |
|