2001-01-08 00:00:00************** UNSAT ******************
  
 ALL NOTES PREVIOUSLY GIVEN!!!
  
 1)NOTE:SHOW TWO CONDIUTS FROM METER TO
 DISCS. YOU SHOW ONE GOING TO PANEL AND
 ONE GOING TO ONE DISC.?????
  
 2)NOTE:ART;210-52D WAS GIVEN FOR REF.
 TO THE BATH CIRCUT REQ`MENTS.
 SEE #12 AND 20 AMP REQ`D.
  
 3)NOTE: AIC RATING OF MAINS REQ`D BY
 110-9/110-10 AND 215-5
  
 4)NOTE:MISSING SMOKE DETECTOR OUTSIDE
 BEDROOM#2
  
 ALSO NOTE IF PLUMB RISER IS ON PLANS
 THEN THEY WILL HAVE TO BE REVIEWED.
  
 PLEASE MAKE THE ABOVE CHANGES AND IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372