Plan Review Notes For Permit 00011063 |
Permit Number |
00011063 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE : THESE ARE THE SAME NOTES AS | | PREVIOUSLY GIVEN. | | AS PER 373-8 DISC. MAY NOT BE USED AS | | A RACEWAY. PLEASE SHOW TWO CONDUIT PATHS | | GOING TO EACH DISC. | | | | 2)NOTE: ALSO AS GIVEN BEFORE,,,,SMOKE | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | ALL SLEEPING ROOMS IN NEW DWELLINGS. | | AS REQ`D BY 1993.1996 NFPA-72 2-2.1.1.1 | | PLEASE SHOW. | | | | 3)NOTE: NEED TO SHOW ON PANEL SCHEDULE | | THE DEDICATED BATH(S) CIRCUT(S)REQ`D | | BY ART:210-52D/215-5 | | | | PLEASE SUBMIT THE ABOVE INDORMATION FOR | | APPROVAL.IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|