Plan Review Notes
Plan Review Notes For Permit 00011063
Permit Number 00011063
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE : THESE ARE THE SAME NOTES AS
 PREVIOUSLY GIVEN.
 AS PER 373-8 DISC. MAY NOT BE USED AS
 A RACEWAY. PLEASE SHOW TWO CONDUIT PATHS
 GOING TO EACH DISC.
  
 2)NOTE: ALSO AS GIVEN BEFORE,,,,SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN NEW DWELLINGS.
 AS REQ`D BY 1993.1996 NFPA-72 2-2.1.1.1
 PLEASE SHOW.
  
 3)NOTE: NEED TO SHOW ON PANEL SCHEDULE
 THE DEDICATED BATH(S) CIRCUT(S)REQ`D
 BY ART:210-52D/215-5
  
 PLEASE SUBMIT THE ABOVE INDORMATION FOR
 APPROVAL.IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372