2001-01-08 00:00:00DENIED;
  
 1.TABLE 407 MINIMUM PLUMBING FIXTURES
 REQUIRED TWO W/C AND ONE LAV. IN BOTH
 MALE AND FEMALE BATHROOMS. ALSO
 REQUIRED IS TWO DRINKING FOUNTAINS
 HIGH LOW DRINKING FOUNTAIN WILL COUNT
 AS TWO FOUNTAINS.
  
 2.DRINKING FOUNTAIN TO MEET REQUIREMENTS
 OF FACBC 4.1.3(10).
  
 3.ICE MACHINE MUST INDIRECTLY DISCHARGE
 TO A FLOOR DRAIN.
  
 4.GAS DIAGRAM REQUIRED SHOWING; TYP. AND
 SIZE OF PIPE, LENGTH OF LONGEST RUN,
 NUMBER OF APPLIANCES, AND BTU'S OF
 EACH AND TOTAL BTU'S.
  