Plan Review Notes For Permit 00011046 |
Permit Number |
00011046 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED; | | | | 1.TABLE 407 MINIMUM PLUMBING FIXTURES | | REQUIRED TWO W/C AND ONE LAV. IN BOTH | | MALE AND FEMALE BATHROOMS. ALSO | | REQUIRED IS TWO DRINKING FOUNTAINS | | HIGH LOW DRINKING FOUNTAIN WILL COUNT | | AS TWO FOUNTAINS. | | | | 2.DRINKING FOUNTAIN TO MEET REQUIREMENTS | | OF FACBC 4.1.3(10). | | | | 3.ICE MACHINE MUST INDIRECTLY DISCHARGE | | TO A FLOOR DRAIN. | | | | 4.GAS DIAGRAM REQUIRED SHOWING; TYP. AND | | SIZE OF PIPE, LENGTH OF LONGEST RUN, | | NUMBER OF APPLIANCES, AND BTU'S OF | | EACH AND TOTAL BTU'S. | | | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 659-8096 EXT. 8377 |
|