Plan Review Notes For Permit 00011046 |
Permit Number |
00011046 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED; | | | | 1.SHUTOFF VALVE REQUIRED FOR COLD WATER | | SUPPLY AT BUILDING. | | | | 2.SHOW COLD WATER TO WATER HEATER ON | | WATER RISER. | | | | 3.GRAB BARS REQUIRED BEHIND WATER | | CLOSETS. | | | | 4.DRINKING FOUNTAIN REQUIRED. SPC 407 | | | | 5.MINIMUM PLUMBING FIXTURES ARE 2 W/C | | FOR MALE 2 W/C FOR FEMALE AND 1 LAV | | IN EACH BATHROOM. | | | | 6.DRINKING FOUNTAIN SHALL COMPLY WITH | | FACBC 4.1.3.10A | | | | 7.SUBMIT GAS DRAWINGS FOR GAS RANGE. | | | | 8.PRIVATE BATHROOM SHALL BE ADAPTABLE | | PER. FACBC SEC. 4.1.3.11. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8377 |
|