Plan Review Notes For Permit 00011046 |
Permit Number |
00011046 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: ALL NOTES FROM PREVIOUS REVIEWS | | HAVE NOT BEEN ADDRESSED. PLEASE SEE | | ALL NOTES ATTACHED. SHOW ALL BRANCH | | CIRCUIT #`S ON PLANS!!!! AND CORRELATE | | WITH PANEL SCHEDULE. | | | | 2)NOTE: LOAD CALCULATIONS HAVE BEEN | | SUBMITTED, BUT ALL CONTINUOUS LOADS | | TO BE SHOWN AT 125% (LIGHTING ETC) | | LOAD CALCULATION SUBMITTED IS UNCLEAR. | | YOU SHOW LOADS FOR FELLOWSHIP HALL AND | | NEW SECOND FLOOR AREA. WHAT ABOUT EXIST- | | -ING AREAS??? PLEASE CLARIFY | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|