Plan Review Notes
Plan Review Notes For Permit 00011046
Permit Number 00011046
Review Stop B
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00BUILDING REVIEW 12/15/2000 J. WITMER
  
 1).503.3 GENERAL AREA MODIFICATION IN-
 CREASES TYPE 5 UNSPRINKLERED BLDG.
 ALLOWABLE AREA 8000 S.F. TOTAL FOOTAGE
 EXISTING STRUCTURE 5060 SQ.FT. ADDITION
 ANOTHER 598 S.F. TOTAL 5658 SQ. FT.
 ALLOWABLE AREA INCREASES NOT REQUIRED.
  
 2). 104.2.2 ADMINISTRATIVE CODE:
 A).PLEASE PROVIDE ADD INFORMATION, PAGE
 5 SHOWS A CROSS SECTION OF A 2ND
 STORY ADDITION. NO INFORMATION IS
 GIVEN ON THE 1ST FLOOR EXTERIOIR
 WALLS AND FOUNDATION FOR THE AREA
 WHERE THE ADDITION IS TO TAKE PLACE.
 B) TYPE 5 BUILDING, IS THIS BUILDING
 FIRE SPRINKLERED FULY OR PARTIALLY?
 C).DISCREPANCIES: SHEET 1 SHOWS THE 2ND
 FL. AS CLASSROOMS VS SHEET 4 AS
 MEETING ROOMS? CLASSROOMS AGE OF
 OCCUPANT?
 3). TABLE 500: A-2 SMALL ASSEMBLY
 TABLE 500 FOR A UNSPRINKLERED BUILD-
 ING ALLOWS FOR A TYPE 5 BUILDING 2
 STORIES. WOOD FRAME CAN ONLY BE A
 SINGLE STORY IF FRAME AND 5000 SF.
 4). 1001.1.3 (NORTH STAIRWAY) MEANS OF
 EGRESS SHALL NOT BE PERMITTED
 THROUGH KITCHENS, CLOSETS, RESTROOMS
 & SIMILAR AREAS NOR THROUGH ADJACENT
 TENANT SPACES.
 5). 1606.4/ 1707.4 MISSLE IMPACT RESIS-
 TANCE GLAZING.
 A).1606.4 GLAZING UNITS TO HAVE LARGE
 MISSLE IMPACT TESTING OR HAVE SHUT-
 TERS THAT HAVE BEEN TESTED & APPROVE
 B).1707.4 WINDOWS NEED TO BE TESTED 10
 SECONDS TO 11/2 THEIR DESIGN PRES.
 6).1606.2.6.2 COMPONENETS & CLADDING
 ROOFING SYSTEMS ARE TO BE TESTED FOR
 110 MPH WIND ZONE. A SBCCI REPORT OR
 DADE COUNTY REPORT ARE REQUIRED.
 7).ADM.CODE 104.2.2 ADDITIONAL INFO.
 REQUIRED, THE EAST WALL OF THE PASTORS
 OFFICE WILL REQUIRE SUPPORT (CBS CON).
 8).2405.2.1.2 GLAZING IN HAZARDOUS LOCA-
 TIONS, SHOWER ENCLOSURES.
 9).2309.6 ATTIC ACCESS REQUIRED, 22 X 36
 WHEN MECHANICAL EQUIPMENT INSTALLED IN
 THE ATTIC, IT SHALL BE IN ACCORDANCE
 WITH 304.4 OF THE MECHANICAL CODE.
 10).HURRICANE ANCHOR SCHEDULE FOR TRUSS
 SHOWING THE NATURE, LOCATION DIRECTION
 & MAGNITUDE OF LOADS TO BE RESISTED.
 11).ASCERTAIN SPECIFIC WINDOW AND DOOR
 BUCK CONNECTIONS FOR WIND RESISTANCE.