2001-01-08 00:00:00 | BUILDING REVIEW 12/15/2000 J. WITMER |
| |
| 1).503.3 GENERAL AREA MODIFICATION IN- |
| CREASES TYPE 5 UNSPRINKLERED BLDG. |
| ALLOWABLE AREA 8000 S.F. TOTAL FOOTAGE |
| EXISTING STRUCTURE 5060 SQ.FT. ADDITION |
| ANOTHER 598 S.F. TOTAL 5658 SQ. FT. |
| ALLOWABLE AREA INCREASES NOT REQUIRED. |
| |
| 2). 104.2.2 ADMINISTRATIVE CODE: |
| A).PLEASE PROVIDE ADD INFORMATION, PAGE |
| 5 SHOWS A CROSS SECTION OF A 2ND |
| STORY ADDITION. NO INFORMATION IS |
| GIVEN ON THE 1ST FLOOR EXTERIOIR |
| WALLS AND FOUNDATION FOR THE AREA |
| WHERE THE ADDITION IS TO TAKE PLACE. |
| B) TYPE 5 BUILDING, IS THIS BUILDING |
| FIRE SPRINKLERED FULY OR PARTIALLY? |
| C).DISCREPANCIES: SHEET 1 SHOWS THE 2ND |
| FL. AS CLASSROOMS VS SHEET 4 AS |
| MEETING ROOMS? CLASSROOMS AGE OF |
| OCCUPANT? |
| 3). TABLE 500: A-2 SMALL ASSEMBLY |
| TABLE 500 FOR A UNSPRINKLERED BUILD- |
| ING ALLOWS FOR A TYPE 5 BUILDING 2 |
| STORIES. WOOD FRAME CAN ONLY BE A |
| SINGLE STORY IF FRAME AND 5000 SF. |
| 4). 1001.1.3 (NORTH STAIRWAY) MEANS OF |
| EGRESS SHALL NOT BE PERMITTED |
| THROUGH KITCHENS, CLOSETS, RESTROOMS |
| & SIMILAR AREAS NOR THROUGH ADJACENT |
| TENANT SPACES. |
| 5). 1606.4/ 1707.4 MISSLE IMPACT RESIS- |
| TANCE GLAZING. |
| A).1606.4 GLAZING UNITS TO HAVE LARGE |
| MISSLE IMPACT TESTING OR HAVE SHUT- |
| TERS THAT HAVE BEEN TESTED & APPROVE |
| B).1707.4 WINDOWS NEED TO BE TESTED 10 |
| SECONDS TO 11/2 THEIR DESIGN PRES. |
| 6).1606.2.6.2 COMPONENETS & CLADDING |
| ROOFING SYSTEMS ARE TO BE TESTED FOR |
| 110 MPH WIND ZONE. A SBCCI REPORT OR |
| DADE COUNTY REPORT ARE REQUIRED. |
| 7).ADM.CODE 104.2.2 ADDITIONAL INFO. |
| REQUIRED, THE EAST WALL OF THE PASTORS |
| OFFICE WILL REQUIRE SUPPORT (CBS CON). |
| 8).2405.2.1.2 GLAZING IN HAZARDOUS LOCA- |
| TIONS, SHOWER ENCLOSURES. |
| 9).2309.6 ATTIC ACCESS REQUIRED, 22 X 36 |
| WHEN MECHANICAL EQUIPMENT INSTALLED IN |
| THE ATTIC, IT SHALL BE IN ACCORDANCE |
| WITH 304.4 OF THE MECHANICAL CODE. |
| 10).HURRICANE ANCHOR SCHEDULE FOR TRUSS |
| SHOWING THE NATURE, LOCATION DIRECTION |
| & MAGNITUDE OF LOADS TO BE RESISTED. |
| 11).ASCERTAIN SPECIFIC WINDOW AND DOOR |
| BUCK CONNECTIONS FOR WIND RESISTANCE. |