Plan Review Notes For Permit 00011046
Permit Number 00011046
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.BOTTLED WATER IS NOT PERMITTED
 IN LIEU OF THE DRINKING FOUNTAIN.
  
 2)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 3)OCCUPANT LOAD SHALL BE DETERMINED FROM
 SPC TABLE 407.SEE SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.PLEASE NOTE
 CORRECT OCCUPANT LOAD ON PLAN.
  
 4)GRAB BARS ARE REQD.BEHIND THE WATER
 CLOSETS PER FACBC SEC.4.16.4.
  
 5)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(100(A).
  
 6)SUBMIT SANITARY RISER THAT COMPLIES W/
 SPC.WATER CLOSETS NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 7)SUBMIT GAS DRAWING FOR GAS RANGE.SEE
 ATTACHED FOR GAS REQS.
  
 8)PRIVATE BATHROOM SHALL BE ADAPTABLE
 PER FACBC SEC.4.1.3.(11).
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER