Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.BOTTLED WATER IS NOT PERMITTED | | IN LIEU OF THE DRINKING FOUNTAIN. | | | | 2)WATER SUPPLY CONTROL SHALL COMPLY W/ | | SPC SEC.610.4.1,610.4.2. | | | | 3)OCCUPANT LOAD SHALL BE DETERMINED FROM | | SPC TABLE 407.SEE SEC.407.1.3.FOR | | ALLOWED DEDUCTIBLE AREAS.PLEASE NOTE | | CORRECT OCCUPANT LOAD ON PLAN. | | | | 4)GRAB BARS ARE REQD.BEHIND THE WATER | | CLOSETS PER FACBC SEC.4.16.4. | | | | 5)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3.(100(A). | | | | 6)SUBMIT SANITARY RISER THAT COMPLIES W/ | | SPC.WATER CLOSETS NOT PERMITTED ON WET | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.911.1.1. | | | | 7)SUBMIT GAS DRAWING FOR GAS RANGE.SEE | | ATTACHED FOR GAS REQS. | | | | 8)PRIVATE BATHROOM SHALL BE ADAPTABLE | | PER FACBC SEC.4.1.3.(11). | | | | IF YOU HAVE ANY QUESTIONS CALL | | 561-659-8096,EXT.8377. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER |
|