Plan Review Notes
Plan Review Notes For Permit 00011046
Permit Number 00011046
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD FOR THIS AREA AND
 TOTAL OCCUPANT LOAD FOR THIS BUILDING.
 SUBMIT NUMBER OF EXISTING PLUMBING
 FIXTURES AND TYPE TO ENSURE COMPLIANCE
 W/TABLE 407 OF SPC FOR ADDED HABITABLE
 FLOOR SPACE.
  
 FIXTURE CLEARANCES FOR ACCESSIBLE TOILET
 ROOMS SHALL COMPLY W/FACBC FIG.28.
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 DRAIN FOR 2ND.FLR TOILETS CANNOT CONNECT
 TO 1ST.FLR.VENT PER S[C SEC.904.1.
  
 SIZE OF SHOWER SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS SEC.409.8.2.1.
  
 FLOOR AND WALLS IN TOILET ROOM SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.(DEPENDING UPON EXIST.FIXTURES
 AND OCCUPANT LOAD.)
  
 CLARIFY EXTENT OF PLUMBING WORK ON 1ST.
 FLOOR.INDICATE IF ANY NEW WORK IS BEING
 DONE OR IF EXISTING.
  
 SUBMIT WATER SUPPLY RISER DIAGRAM FOR
 REVIEW.WATER SUPPLY CONTROL SHALL COMPLY
 W/SPC SEC.610.4.1.,610.4.2.