Plan Review Notes For Permit 00011046 |
Permit Number |
00011046 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD FOR THIS AREA AND | | TOTAL OCCUPANT LOAD FOR THIS BUILDING. | | SUBMIT NUMBER OF EXISTING PLUMBING | | FIXTURES AND TYPE TO ENSURE COMPLIANCE | | W/TABLE 407 OF SPC FOR ADDED HABITABLE | | FLOOR SPACE. | | | | FIXTURE CLEARANCES FOR ACCESSIBLE TOILET | | ROOMS SHALL COMPLY W/FACBC FIG.28. | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | ROOMS PER SPC SEC.409.4.1.1. | | | | DRAIN FOR 2ND.FLR TOILETS CANNOT CONNECT | | TO 1ST.FLR.VENT PER S[C SEC.904.1. | | | | SIZE OF SHOWER SHALL COMPLY W/COUNTYWIDE | | AMENDMENTS SEC.409.8.2.1. | | | | FLOOR AND WALLS IN TOILET ROOM SHALL BE | | NONABSORBENT TO A HEIGHT OF 4'PER SBC | | SEC.1204.2. | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.(DEPENDING UPON EXIST.FIXTURES | | AND OCCUPANT LOAD.) | | | | CLARIFY EXTENT OF PLUMBING WORK ON 1ST. | | FLOOR.INDICATE IF ANY NEW WORK IS BEING | | DONE OR IF EXISTING. | | | | SUBMIT WATER SUPPLY RISER DIAGRAM FOR | | REVIEW.WATER SUPPLY CONTROL SHALL COMPLY | | W/SPC SEC.610.4.1.,610.4.2. |
|