2001-01-08 00:00:00****************************************
  
 1]ASSEMBLY OCCUPANCY REQUIRES TWO
 SEPERATE AND REMOTE EXITS FROM EACH
 STORY,SEE SECTIONS 1004.1.4AND1004.2,
 ALSO 1001.1.3,1997 SBC.
 2]SHEET 3 SHOWS A DEAD END HALLWAY,20'
 LONG NOT PERMITTED PER SECT.1005.2.
 3]PROVIDE DETAIL SPECIFYING OLD ROOF
 JOIST/NEW FLOOR JOIST SIZE AND SPACING
 LAYOUT.
 4]PLEASE CLERIFY PREFAB BEAM AND POST
 COMMENT ON SHEET 4[EXISTING,NEW,BEARIN
 POINTS].
 5]CERTIFY ADDITIONAL LOADS IMPOSED ON
 EXISTING ONE STORY CONSTRUCTION.