Plan Review Notes For Permit 00011033 |
Permit Number |
00011033 |
|
Review Stop |
FIRE |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2001-01-29 00:00:00 | PREVIOUS NOTES TRANSFERRED TO PERMIT | | #01011195.REVIEW WAS DONE UNDER | | "SHELL" PERMIT...NEEDED TO APPLY FOR | | NEW PERMIT, MECH. ENG. CHANGED. | | PHK. | 2001-01-10 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED ON | | SHEET A-001. SHOULD READ 1985 EDITION | | INSTEAD OF 1994 EDITION. | | 2) PROVIDE SEPARATE PLANS AND PERMIT FOR | | FIRE SPRINKLER REMODEL. | | 3) PROVIDE SEPARATE PLANS AND PERMIT FOR | | FIRE ALARM EQUIPMENT SHOWN ON DRAWINGS. | | SYSTEM TO BE CLASS A OR ADDRESSABLE. CUT | | SHEETS, WIRING DIAGRAM, FLOOR PLANS, AND | | BATTERY CALCULATIONS ARE TO BE PROVIDED. | | 4) PLEASE CLEARLY IDENTIFY EMERGENCY | | LIGHTING LOCATIONS WITHIN TENANT SPACE. | | 5) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR TENANT | | SPACE. | | 6) PLEASE DISPLAY LOCATIONS OF PORTABLE | | FIRE EXTINGUISHERS. PLEASE PROVIDE | | RATING FOR EXTINGUISHERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|